36
Fig. 29.
•
Code 05 - ECO mode selection.
Fig. 30.
Parameter 3 setting: Activates or deactivates the ECO
function.
–
DIS. ECO function disabled.
–
ENA. ECO function enabled.
If the ECO function is disabled, the voltage and
frequency range for ECO mode can be adjusted, but
there is no point unless the function itself is enabled.
•
Code 08 - Bypass mode setting.
Fig. 31.
Parameter 2 setting.
–
OPN. Bypass permitted. When selecting this option,
the UPS will operate in bypass mode, provided that
selection in bypass settings (parameter 3) has been
enabled/disabled.
–
FBD. When selecting this option, operation in
bypass mode is not permitted in any condition.
Parameter 3 setting:
–
ENA. Bypass enabled. When selected, bypass
mode is enabled.
–
DIS. Bypass disabled. If selected, automatic bypass
is permitted but not manual switch to bypass.
At this point, manual switch to bypass is understood
as being that which users perform on the UPS. For
example, pressing the OFF button on the front of the
device when it is in AC mode transfers the load to
the static bypass.
•
Code 09 - Maximum battery discharge time setting.
Fig. 32.
Parameter 3 setting:
–
000 ~ 999. Sets maximum backup time. The UPS
will turn off automatically once it has elapsed
to protect the batteries. The default value is 990
minutes (16.5 h).
–
DIS. Disables the battery discharge time protection
and the backup time will depend on the capacity of
the batteries.
•
Code 10 - Reserved.
Fig. 33.
Reserved for future options.
•
Code 11 - Reserved.
Fig. 34.
Reserved for future options.
•
Code 12 - Hot standby function.
Fig. 35.