Fixing details
Read all the installation instructions before commencing with the installation. The
installation of this panel must be carried out by a suitably qualified /trained person. The
installation must comply with IEE wiring regulations and with BS5839 part 1 2002
The electronic components within the fire panel are Static Sensitive. Do not
touch the electronics directly.
Mounting the Backbox
The COP3000 can be flush mount or surface mounted.
1, Surface Mount;
drill four holes and fix the backbox to the wall.
2, Flush mounting the backbox requires a hole 364x 472 with a depth of 117mm
(standard battery / backbox ) or 217 mm if deep backbox is used.
Installing Cabling
Once the backbox is mounted the next stage is to install the power and loop cables and
fit the glands.
364mm
227mm
309mm
472mm
479mm
400mm
117mm
132mm
23