Optional Functions as per EN54 P2&4
Inputs
Input 1: Reset
This input is used to reset the control and indicating equipment
Input 2: Testing of Fire Routing Equipment
This input is used to test the output to the fire routing equipment
Input 3: Disablement of the Fire Routing Equipment
This input is used to disable the fire routing equipment output of the COP3000. Whilst the FRE is
disabled by this input, it can not be re-enabled by the COP3000 control panel
Input 4: Disablement of the Fire Protecting Equipment
This input is used to disable the fire protecting equipment output of the COP3000. Whilst the FRE
is disabled by this input, it can not be re-enabled by the COP3000 control panel
Input 5: Disablement of Sounders
This input is used to disable the sounders of the COP3000. The disablement of sounders from the
Fire Brigade Panel can be re-abled from the COP3000 control panel only when the system is not
Alarm State.
Output 4: Disablement of the Fire Routing Equipment
This output is ON to indicator that the fire routing equipment has been disabled either by the
COP3000 Control and indicating equipment or the Fire Brigade Panel.
Output 5: Reset from Fire Alarm Condition
This output is ON to indicate that the COP3000 control and indicating Equipment is in alarm
condition. This output will remain on for at least 15mins after reset or when the reset has been
activated from the Fire Alarm Brigade Panel
Output 6: Disablement of Sounders
This output is ON to indicate that the sounders have been disabled either by the COP3000 control
and indicating equipment or the Fire Brigade Panel.
20
Summary of Contents for COP3000
Page 3: ...Installation Section 1 3 www acornfiresecurity com www acornfiresecurity com...
Page 28: ...Panel Assembly Information Section 2 28 www acornfiresecurity com www acornfiresecurity com...
Page 33: ...Appendix Section 3 33 www acornfiresecurity com www acornfiresecurity com...
Page 39: ...System Wiring 106 39 www acornfiresecurity com www acornfiresecurity com...