relay).It is current limited to 30 mA.
Under fault conditions or even if the COP3000 is powered down, this output will be switch to O
volts.
Ensure the polarity of the connections is observed at all times and end of line resistors ( 6K8 5% )
are fitted for correct operation.
Delays to outputs (Option 7.11 of EN54pt 2)
The COP3000 has the option to delay the operation of panel sounders, the fire routing equipment
output and the fire protecting Equipment. This delay is selectable using the COP3000 site installer
download software .The delay is configurable in increments of 1 minute up to a maximum of 10
minutes.
This delay can be enabled and disabled at access level 2.
The COP3000 has the facility for a specific call point to override this delay by programming this call
point via an input interface to provide an evacuate signal using COP3000 site Installer.
Coincidence Detection (Option 7.12 of EN54 pt 2)
The COP3000 has the facility to inhibit the operation of the output sounders, Output to Fire routing
equipment and the output of the fire protecting equipment until one more confirmatory signals are
received from different zones. This feature is programmable using COP3000 Site Installer
Software.
Optional Functions as per EN54 P2&4