SICLI COP3000 Installation Manual Download Page 16

End of Line resistor                                                

 

 : 6k8

Fire Protecting Equipment

Max Load                                                               

 

 : 60 mA

Fused  (PTC3)                                                            

 : 100 mA Polyswitch

End of Line resistor                                               

 

 : 6k8

Fault  Routing equipment

Max Load                                                             

 

 : 30 mA

Fused  (PTC1)                                                             

 : 100 mA Polyswitch

End of Line resistor                                             

 

 : 6k8

Auxiliary Relays

The auxiliary relays provide fused volt free change over contacts. These contacts are not monitored.
Max Load                                                             

   

 : 24 Volts 1 Amp

Fuse  (PTC4)                                                         

 

 : 1.35 Amps Polyswitch

Auxiliary 24V Supply

Nominal Voltage          

 

 

 

 

 : 24 Volts ±10%

Fuse (PTC5)   

 

 

 

 

 

 : 100 mA Polyswitch

Maximum current  

 

 

 

 

 

 : 30 mA

This output is not to be used for Fire protecting equipment or Fire alarm routing Equipment
Any power taken from the alarm system will effect the standby duration

RS485 Port

This is a serial output port for driving COP6000 Repeater panels, mimics etc..
This output is short circuit protected
Max Cable Length      

 

 

 

 

 : 2 Km

Min Recommended cable size 

 

 

 

 : 1 mm² (Screened)

RS232 Port

This is a serial output port for driving COP6000 Repeater panels, mimic etc..
This output is short circuit protected

Printer

 (Optional)

Type   

 

 

 

 

 

 

: High speed thermal

Number of Characters per Line  

 

 

 

: 40

Type of paper               

 

 

 

 

: 58mm x 46mm Thermal Roll 

Replacement paper roll order code   

 

 

: .ADF6PRINTERPAPER

Mechanical Specification

Weight including batteries 

 

 

 

 

 : 18 Kg

Weight excluding batteries 

 

 

 

 

 : 9 Kg

Dimensions (Standard batteries) 

 

 

 

 : 495 mm (L) x 395 mm(H) x 180 mm(D)

Type of Material (backbox) 

 

 

 

 

 : Mild Steel (Power Coated)

Type of Material (Facia) 

 

 

 

 

 : PC/ABS

Flammability Rating                            

   

 

 : UL 94 V0

Total Number of knockouts 

 

 

 

 

 : 51

Diameter of Knock out   

 

 

 

 

 : 20 mm

Anti-Tamper Cover ( Optional)

Weight  

 

 

 

 

 

 

 : 250 g

Material used   

 

 

 

 

 

 : Polycarbonate

Flammability Rating                              

 

 

 : UL 94 5VA

TERMINAL BLOCKS : DO NOT USE EXCESSIVE FORCE WHEN TIGHTENING THE SCREWS ON 
THE TERMINAL BLOCK

 

 

 

 

 

 

 

CAUTION

 

 

 

 

RISK OF EXPLOSION IF BATTERY IS REPLACED

 

 

 

 

 

 

BY AN INCORRECT TYPE

 

 

 

 

DISPOSE OF THE USED BATTERIES ACCORDING

 

 

 

 

 

 

TO THE INSTRUCTIONS

Technical Specification

16

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for COP3000

Page 1: ...ALLATION MANUAL Document Ref 25 17191 A SA SICLI Rue du Merlo 1 1180 Bruxelles Tel 02 370 24 11 Fax 02 370 24 24 Internet www sicli be ANALOG FIRE CONTROL PANEL www acornfiresecurity com www acornfire...

Page 2: ...nnections 24 Networking 25 Inputs Outputs 27 2 0 Panel Assembly Information 28 Attaching Panel Door 29 Installing Screen Door 30 Replacing Printer Paper Roll 31 Panel Fault finding 32 3 0 Appendix 33...

Page 3: ...Installation Section 1 3 www acornfiresecurity com www acornfiresecurity com...

Page 4: ...day The status LED can be programmed to either be permanently off under normal conditions or to pulse in order to confirm that it is in communication with the COP3000 control panel The range of compa...

Page 5: ...sting of a combined sounder base with a maximum output of 95 dB A a standalone sounder with a maximum output of 100 dB A that is available in standard or weatherproof versions and a stand alone loop p...

Page 6: ...d as a discreet stand alone wall or ceiling mounted device The sounder base design incorporates a mechanism that can be activated if required to lock either the Sensor or the cover into place to preve...

Page 7: ...open or short circuit conditions are monitored and generate a system fault signal Inputs are suitable for use as fire signal inputs such as from a sprinkler flow switch however they can also be used t...

Page 8: ...to Sicli Please refer to local standards for details of the maximum allowable area to be covered by a single zone COPZMU IS fixes to a standard deep double gang back box and can be either surface or s...

Page 9: ...ontrol of the sounder operation without having to wire the sounder back to the COP3000 control panel A 4 way unit takes up a single address but each circuit can be independently controlled A COP4SIR u...

Page 10: ...external equipment External relays should be suppressed If a non suppressed relay is used then a diode can be connected as shown in the wiring diagram in the appendix to suppress any reverse EMF on t...

Page 11: ...lation guidelines must be followed 1 External cables must be connected using the cable entries or knockouts provided 2 When routing external cables inside the product they must be a Kept as short as p...

Page 12: ...LED s designed to give clear status information to non technical users User configuration and maintenance facilities COP3000 has comprehensive facilities for on site system configuration whereby the...

Page 13: ...side of the short circuit will operate and the COP3000 control panel will drive communication from both ends of the loop Simple future expansion COP3000 is designed to ensure simplicity of future exp...

Page 14: ...ate is used to cover the printer paper aperture to enhance the appearance of COP3000 and to preserve its ingress protection rating Hinged lockable cover With a standard panel access to all panel funct...

Page 15: ...Surge F4 Maximum battery current 3 5 Amps Standby current mA 175 4 loops 125 2 loops Maximum Charging Current to the Batteries 1 0amp Float Voltage 27 4 Volts Final Voltage 21 0Volts Charging Charact...

Page 16: ...e 1 mm Screened RS232 Port This is a serial output port for driving COP6000 Repeater panels mimic etc This output is short circuit protected Printer Optional Type High speed thermal Number of Characte...

Page 17: ...splay and will remain until the fire alarm is reset Ensure the polarity of the connections are observed at all times and end of line resistors 6K8 5 are fitted for correct operation Output to Fire Ala...

Page 18: ...able in increments of 1 minute up to a maximum of 10 minutes This delay can be enabled and disabled at access level 2 The COP3000 has the facility for a specific call point to override this delay by p...

Page 19: ...n alarm condition to indicate that the COP3000 Control and indicating equipment has operated the AUX output Output 2 Fire Routing Equipment operated Fire Brigade Link This output is ON in alarm condit...

Page 20: ...is input is used to disable the sounders of the COP3000 The disablement of sounders from the Fire Brigade Panel can be re abled from the COP3000 control panel only when the system is not Alarm State O...

Page 21: ...should NEVER be run within the same cable 7 Loop feeds and returns should NEVER be used within the same cable Cable Resistance Cable Anchorage The mains cable must be fixed securely with a 20mm cable...

Page 22: ...ided on each device to facilitate this The screen should be earthed at the connection point provided at the COP3000 panel and not at any other point Both the loop start and the loop end must be connec...

Page 23: ...ve Do not touch the electronics directly Mounting the Backbox The COP3000 can be flush mount or surface mounted 1 Surface Mount drill four holes and fix the backbox to the wall 2 Flush mounting the ba...

Page 24: ...ng WARNING THE FIRE ALARM SUPPLY REMAINS LIVE WHEN THIS SWITCH IS TURNED OFF Or b If the isolating protective device is fed from the dead side of the main isolating device a label should be fixed to t...

Page 25: ...very panel silencing and resetting of alarms can also be carried out from any panel on a networked system if panels are suitably configured Networked panels are connected using a loop topology as illu...

Page 26: ...5 Amp All outputs are fused with 1 6 Amp Glass fuse Alarm devices should be spread equally across the 4 sounder circuits WARNING DO NOT EXCEED THE RATED OUTPUT CURRENT OUTPUT FIRE ALARM ROUTING EQUIPM...

Page 27: ...are fused with 1 6 Amp Glass fuse Alarm devices should be spread equally across the 4 sounder circuits WARNING DO NOT EXCEED THE RATED OUTPUT CURRENT OUTPUT FIRE ALARM ROUTING EQUIPMENT OPTION 7 9 EN...

Page 28: ...Panel Assembly Information Section 2 28 www acornfiresecurity com www acornfiresecurity com...

Page 29: ...signed as a drop on fit Offer the door up to the back box in the open position as shown below Align the hinges and lower the door onto the hinge pins Check the hinges are secure 29 www acornfiresecuri...

Page 30: ...ch or retro fitted later The method for fitting a cover is shown below Insert the bottom peg of the hinged cover into the panel as shown and close the hinged cover followed by the printer door Next fr...

Page 31: ...paper through if the panel is powered up Tear off the excess paper them close and secure the printer access door Please note for paper feed to operate correctly paper end must be straight New paper ro...

Page 32: ...6V Mon 28V Fire Depends on Programming 0 6V Mon 28V Fire Depends on Programming 0 6V Mon 28V Fire Depends on Programming Static Conditions No Data 9V 0V 9V 0V 0V No Data See Scope Plots for Monitoring...

Page 33: ...Appendix Section 3 33 www acornfiresecurity com www acornfiresecurity com...

Page 34: ...cuit board 3 Connect the unit according to the diagram below Notes No addressing of the interface is required See control panel operation for details This unit requires a permanent 230V AC supply Stan...

Page 35: ...pass the wires into it 4 Connect the unit according to the diagram below Notes No addressing of the interface is required See control panel operation for details Standard Connections Notes 1 This uni...

Page 36: ...e unit according the diagram below Notes No addressing of the interface is required See control panel operation for details Standard Connections E E 22k 5k6 E C N C N O IN OUT Analogue Addressable Loo...

Page 37: ...iculty is experienced when mounting the sensor this may be due to the following Wiring causing an obstruction move or shorten wires Although the base is tolerant to uneven mounting surfaces a very une...

Page 38: ...2 LOOP 4 AUX RELAY LOOP CIRCUITS 0V S S F F F F S S 26V Rx CTS RTS OV Tx Tx Tx S F F S S F F S 1 2 SOUNDER CIRCUIT 2 MODEM PC Rs232 MIMIC REPEATER 1 2 System Wiring 38 LOOPSPLITTER L1A L1B L1C L1D L2A...

Page 39: ...System Wiring 106 39 www acornfiresecurity com www acornfiresecurity com...

Page 40: ...ket fits inside the base Connection WARNING Do NOT use high voltage testers if ANY equipment is connected to the system Earth scrreen must be continuous along entire length of loop NOTE Care should be...

Page 41: ...UF FP200 or MICC Standby current 320 uA Operating temperature 10 to 55 degrees C 95 RH Sound output 3dB Low volume 84dB 4mA set by panel Medium volume 92dB 8mA High volume 95dB 12mA Tones Continuous 9...

Page 42: ...and pass the wires into it 4 Connect the unit according to the diagram below Notes No addressing of the interface is required See control panel operation for details Standard Connections Notes 1 Only...

Page 43: ...Call Point COPBG S COPBG SY COPBG WP E E IN OUT Analogue Addressable Loop LOOP IN LOOP OUT 43 www acornfiresecurity com www acornfiresecurity com...

Page 44: ...eral FAULT System DISABLE System FAULT System TEST Charge FAULT Battery FAULT 1 2 3 4 5 6 7 8 9 21 22 23 24 10 11 12 13 14 15 16 17 18 19 20 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44...

Page 45: ...to repair any batteries they should be treated as disposable when they have outlived their use Batteries must be disposed of in accordance with current waste disposal and pollution legislation and in...

Reviews: