Optional Functions as per EN54 P2&4
COP3000 is approved to EN54 Parts 2 & 4 including all the following options which can be selected
as required
Panel Outputs
Panel Sounders: (OPTION 7.8 EN54 PT 2)
Two pairs of outputs are provided. ONLY polarised equipment should be used.
Ensure the polarity of the connections are observed at all times and end of line resistors (6K8 5%)
are fitted for correct operation.
The total alarm load across all sounder outputs = 1.5 Amp
All outputs are fused with 1.6 Amp Glass fuse Alarm devices should be spread equally across the
4 sounder circuits.
WARNING: DO NOT EXCEED THE RATED OUTPUT CURRENT
Output Fire Alarm Routing Equipment (Option 7.9 EN54 PT 2)
This output, which is fused, and monitored using a 6.8k end of line resistor, is used for the
automatic transmission of the fire signals to fire alarm routing equipment (e.g. Fire brigade). It
operates by providing 24 Volt output to an auxiliary device ( e.g. relay).
It is current limited to 30 mA using a resettable polyswitch. Class change and test conditions do
not operate this output. If operated under a fire alarm condition, the indication will be displayed on
the Touch screen display and will remain until the fire alarm is reset.
Ensure the polarity of the connections are observed at all times and end of line resistors ( 6K8 5% )
are fitted for correct operation.
Output to Fire Alarm Protecting Equipment (Option 7.10 EN54 PT 2)
This output, which is fused, and monitored using a 6.8k end of line resisters used for the
transmission of the fire signals to controls for automatic fire protecting equipment (e.g. Door
released units etc).It operates by providing 24 Volt output to an auxiliary device ( e.g. relay).
It is current limited to 30 mA using a resettable. polyswitch. Class change and test conditions do
not operate this output. If operated under a fire alarm condition , this output remains energised
until the fire alarm is reset.
Ensure the polarity of the connections is observed at all times and end of line resistors ( 6K8 5% )
are fitted for correct operation.
Output to Fault Warning Routing Equipment (Option 9.4.1C EN54 PT
2)
This output, which is fused and monitored using 6.8k end of line resistor, is used for the
transmission of fault signals to fault warning routing equipment This output is monitored using 6k8
end of line resistor and it current limited to 30 mA.Under normal condition it operates by providing
12vdc which can be connected directly to a 12v auxiliary device.
17
Summary of Contents for COP3000
Page 3: ...Installation Section 1 3 www acornfiresecurity com www acornfiresecurity com...
Page 28: ...Panel Assembly Information Section 2 28 www acornfiresecurity com www acornfiresecurity com...
Page 33: ...Appendix Section 3 33 www acornfiresecurity com www acornfiresecurity com...
Page 39: ...System Wiring 106 39 www acornfiresecurity com www acornfiresecurity com...