11.7.6.1
Smart Task SLTI Version
Table 38: Smart Tasks - SLTI Version
ISDU
Name
Data type
Data Stor‐
age
Length
Access
Default
value
Value/range
Index
Sub-
index
DEC
HEX
1080
438
-
SLTI Version
String
-
8 bytes
ro
-
-
The
SLTI version
contains the version number for the Smart Task
Basic logic
.
11.7.6.2
Smart Tasks Input selector
Table 39: Smart Tasks - Input selector
ISDU
Name
Data type
Data Stor‐
age
Length
Access
Default
value
Value/range
Index
Sub-
index
DEC
HEX
1081
439
-
Input selector 1
UInt
1 Byte
rw
0
0 = Module 1 Qint.1
1 = Module 1 Qint.2
2 = Module 2 Qint.1
3 = Module 2 Qint.2
4 = Module 3 Qint.1
5 = Module 3 Qint.2
6 = Module 4 Qint.1
7 = Module 4 Qint.2
8 = Module 5 Qint.1
9 = Module 5 Qint.2
10 = Module 6 Qint.1
11 = Module 6 Qint.2
12 = Module 7 Qint.1
13 = Module 7 Qint.2
14 = Module 8 Qint.1
15 = Module 8 Qint.2
16 = Module 9 Qint.1
17 = Module 9 Qint.2
18 = Module 10 Qint.1
19 = Module 10 Qint.2
20 = Module 11 Qint.1
21 = Module 11 Qint.2
22 = Module 12 Qint.1
23 = Module 12 Qint.2
24 = Module 13 Qint.1
25 = Module 13 Qint.2
26 = Module 14 Qint.1
27 = Module 14 Qint.2
28 = Module 15 Qint.1
29 = Module 15 Qint.2
30 = Module 16 Qint.1
31 = Module 16 Qint.2
64 = Ext.input 1
1082
43A
-
Input selector 2
1 Byte
64
The settings for
Input selector 1
and
Input selector 2
can be used to logically link the sensor’s internal detection signal
Qint.1
,
Qint.2
,
Qint.3
or
Qint.4
to another sensor’s switching signal read via pin 2.
To do this,
Pin 2 configuration
(ISDU 121) must be set to
External input
.
NOTE
If no physical signal is applied to the external input or if another function is selected for
Pin 2 configuration
(ISDU
121), the status of the external input is interpreted as logical 0.
NOTE
Dependency:
•
Pin 2 configuration
(ISDU 121)
11
ANNEX
56