NOTE
Assign the functions for the digital inputs in the device using SICK AppStudio.
13.3.8
Wiring digital outputs of the device in the CDB650-204
Device = InspectorP64x = V2D64xP-xxxxAx
Device = InspectorP65x = V2D65xP-xxxxAx
These digital outputs can be parameterized independently as IN and OUT. Default: IN
Device
1
CDB650-204
Load (e.g. PLC)
4
Cable
3
B
1
.
.
.
D
22
GND
5
Shield
U
IN
*
V
S
GND
V
out
Result
A
GND
B
1
2
2
For inductive load:
6
3
1
7
2
6
5
4
8
13
14
17
15
9
10
12
16
11
3
1
7
2
6
5
4
8
13
14
17
15
9
10
12
16
11
RES/OUT
C
8
7
2
5
Filter
Figure 17: Wire the digital output in the CDB650-204 connection module.
1
Device
2
Supply voltage V
S
3
Connection cable 1:1 (female connector, M12, 17-pin, A-coded/male connector, M12, 17-pin, A-coded)
4
Load (e.g. PLC)
5
Output voltage V
out
6
With inductive load: see note
7
Connection module: female connector, M12, 17-pin, A-coded
8
Device: male connector, M12, 17-pin, A-coded
Inductive load
NOTE
Provide an arc-suppression switch at the digital output if inductive load is present.
b
Attach a freewheeling diode directly to the load for this purpose.
Table 15: Assignment of placeholders to the digital outputs
Device
CDB650-204
Output A
Pin B
Signal C
Terminal D
IN/OUT 3
13
RES/OUT 1
20
IN/OUT 4
14
RES/OUT 2
21
IN/OUT 5
16
RES/OUT 3
50
IN/OUT 6
17
RES/OUT 4
51
ANNEX
13
8019943/1EJ6/2022-02 | SICK
O P E R A T I N G I N S T R U C T I O N S | InspectorP64x/65x
57