8.3.3
Menu tree Parameter
Menu level
Explanation
Parameters
Parameter
Settings
Parameter settings/display of system compo‐
nents
Physical Unit
Component
Unit
mg/m3, ppm
Ref. condition
•
t: actual, 25 °C, 20 °C, 0 °C
•
p: actual, 1013 mbar
•
Hum.: wet, dry
Average
Avg. Time
0 ... 300 s
Meas. Distance
Active
200 ... 8000 mm
Gas temperature
Source
Probe, Subst. Analog In
Subst.
–100 ... 2000 °C
Pressure
Source
Probe, Subst. Analog In
Subst.
600 ... 15000 hPa
Humidity
Subst.
Subst.: 0 ... 93.0 percent by volume
Analog Out
Live Zero
0, 4 mA
Output 1
Component: e.g.. NH
3
, - -, p, T
Range low: 0 ... 999999
Range high: 0 ... 999999
Cycle Out: No, Yes
Output 2
Component: e. g. NH
3
,, - -, p, T
Range low: 0 ... 999999
Range high: 0 ... 999999
Cycle Out: No, Yes
Output 3
Component: e. g. NH
3
,, - -, p, T
Range low: 0 ... 999999
Range high: 0 ... 999999
Cycle Out: No, Yes
OPERATION
8
8019532/100Q/V1-1/2018-08 | SICK
O P E R A T I N G I N S T R U C T I O N S | GM700 Ex
61
Subject to change without notice