Technical specifications
Minimum
Typical
Maximum
Total current I
sum
ΣI
Qn
, T
A
≤ 45 °C
–
–
4 A
ΣI
Qn
, T
A
≤ 55 °C
–
–
3.2 A
Load diagram for the Q1 to Q4 outputs of the
UE410-MU/UE410-XU modules
Test pulse width
500 μs
640 μs
700 μs
Test pulse frequency
12.5 Hz
–
32 Hz
Inductive switch-off energy
E = 0.5 × L × I²
–
–
370 mJ
Load capacity
–
–
500 nF
Cable length (single,
⊕
1.5 mm
2
)
–
–
100 m
Response time (I1/I2)
program
3.1, 7, 8
–
–
13 ms
Response time (I1/I2)
16)
program
1, 2, 4, 5, 6, 9
–
–
29 ms
Response time (I1/I2)
16)
program
1 pressure sensitive mat
–
–
38 ms
Response time of all programs
with tested ESPE Cat. 4 (e.g. L41)
–
–
56 ms
Response time (I3/I4)
16)
program 1, 2, 7, 8, 9
–
–
13 ms
Response time (I3/I4)
16)
program 4, 5
–
–
29 ms
Response time (I1-X1, I2-X2)
16)
program 3.2
–
–
79 ms/29 ms
Response time
on connection of
Flexi Loop
56 ms
16)
Time without sensor, the data for the sensors connected apply in addition.
17)
Response time not including Flexi Loop and not including sensor. Also take into account the response times of
Flexi Loop and the sensors connected.
Total current per temperature
Σ I
Qn
[A]
T
A
[°C]
T
A max