Technical specifications
11.1.3
UE410-8DI input extension module
Minimum
Typical
Maximum
Supply circuits (via UE410-MU or UE410-GU)
Power consumption
–
–
3 W
Input circuit (I1-I8)
Number of inputs
–
–
8
Input voltage (high)
13 V DC
–
30 V DC
Input voltage (low)
–5 V DC
–
5 V DC
Input current (high)
2.4 mA
3 mA
3.8 mA
Input current (low)
–2.5 mA
–
2.1 mA
Input capacitance
9 nF
10 nF
11 nF
Minimum switch-off time
See response times
Break time of the input signal
without switching of the outputs
–
–
1 ms
Monitoring of synchronisation,
switch position 3, 5
–
1500 ms
–
Power-up delay
70 ms
–
–
Reset time
–
–
120 ms
Output circuit (X1-X8)
Number of outputs
–
–
8
Type of output
PNP semiconductors, short-circuit protected, cross-
circuit detecting
Output voltage
16 V DC
–
30 V DC
Output current
–
–
30 mA
Test period
–
–
40 ms
Load capacity
–
–
1,000 nF
Cable resistance
–
–
100 Ω
Response time UE410-8DI on safety outputs UE410-MU/UE410-XU (Q1-Q4)
Response time
switch setting 6, 7
–
–
17 ms
Response time
switch setting 1, 2, 3, 4, 5, 8
29)
–
–
34 ms
Response time switch setting 2
pressure sensitive mat
29)
–
–
42 ms
Response time of all programs
with tested ESPE Cat. 4 (e.g. L41)
–
–
60 ms
Response time
on connection of
Flexi Loop
60 ms
27)
Cross circuit detecting only within a module.
28)
The total output current for a Flexi Classic system is limited. The current for supplying all sensors that are
connected to the UE410-MU/XU (X1/X2) and UE410-8DI (X1-X8) must be I < 600 mA and the current on a
Flexi Classic gateway must be I<100 mA. If this total current is insufficient, please contact the SICK hotline.
29)
Time without sensor, the data for the sensors connected apply in addition.
Tab. 43: Data sheet
UE410-8DI