CONFIGURING
4
Switch to the “Configuration / Application selection” directory (
MCU/Configuration/Application selection”, page 72
5
The basic type of the sender/receiver unit connected is displayed in the “Connected
variant” window (field “Application selection”). Click “Save selection” to assign to the
control unit
.
Fig. 35: SOPAS ET menu: MCU/Configuration/Application selection
9.4.3
Factory settings
Table 13: Factory settings
The steps required to modify these settings are described in the following Sections. For this
purpose, the devices must be connected in SOPAS ET (
), the Level
1 password set and the “Maintenance” mode set.
Parameter
Value
Function check
Every 8 h; output of control values (every 90 s)
on standard analog output
Analog output (AO)
[mA]
Live Zero (LZ)
4
Measuring range end value
(MBE)
20
Current during maintenance
0.5
Current by malfunction
21 (optional 1)
Response time
60 s for all measured variables
Measured variable
Output on AO
Value at LZ
Value at MBE
Dust concentration [mg/m³]
1
0 200
Scattered light intensity
2
Coefficients set (only for dust concentration)
0.00 / 1.00 / 0.00