1
0
1
2
near
far
Figure 29: Centering function for the example “window not inverted.”
1
Old center point before centering teach
2
New center point after centering teach
Available under
SOPAS ET: “Output settings” page
IO-Link:
•
Index 94 (0x5E) “Q1 center of window”
•
Index 95 (0x5F) “Q2 center of window”
•
Index 96 (0x60) “Qa center of analog output”
•
Index 130 (0x82) “Teach”
•
Index 131 (0x83) “Teach status”
6.4.9.2
Switching delay
For the output functions Q
1
and Q
2
, a time function can be activated. The configured
time function applies to both switching outputs. The following functions are available:
Deactivated
Right after the measured distance has exceeded the specified switching point, the state
of the switching output changes (factory setting).
Switch-on delay
The changeover of the switching output from an inactive to an active state is time-
delayed. The delay time is adjustable. The changeover from an active to an inactive
state is not delayed.
Switch-off delay
The changeover of the switching output from an active to an inactive state is time-
delayed. The delay time is adjustable. The changeover from an inactive to an active
state is not delayed.
ON and OFF delay
The changeover from an inactive to an active state and vice versa is time-delayed. The
delay time is adjustable.
One-time timer
Once the switching condition has been met, the switching output changes from an inac‐
tive to an active state. The switching output remains in an active state for a specified
period regardless of how long the switching condition is met. It does not switch back
to an inactive state until this time has elapsed. Any additional changes made to the
switching condition during this period are still not taken into account.
6
OPERATION
68
O P E R A T I N G I N S T R U C T I O N S | DT50-2 Pro
8017154/1AVV/2021-03-24 | SICK
Subject to change without notice