6.4.4.1.4
Operating examples via display: Scaling the analog output with respect to the distance value
output
Use Easy Teach to teach in the current distance for “4 mA” in the menu
Operating example or steps:
RUN mode
Press for 5 sec. → 4 mA
Position object
→ Saved
Necessary default settings:
Factory setting or function Q
2
/Q
a
=
4-20 mA
Mode Q
a
= Distance (only for user
level = Advanced)
Factory setting:
200 mm
Use Easy Teach to teach in the current distance for “20 mA” in the menu
Operating example or steps:
RUN mode
Press for 5 sec. → 20 mA
Position object
→ Saved
Necessary default settings:
Factory setting or function Q
2
/Q
a
=
4-20 mA
Mode Q
a
= Distance (only for user
level = Advanced)
Factory setting:
30,000 mm
Teach in the current distance for “4 mA” in the menu
Operating example or steps:
RUN mode
→ Q
1
Output
/
to → Q
2
Output
→ Function Q
2
/Q
a
/
to → Teach Q
a
→ 4 mA
Position object
→ Saved
to → RUN mode
Necessary default settings:
Factory setting or function Q
2
/Q
a
=
4-20 mA
Mode Q
a
= Distance (only for user
level = Advanced)
Factory setting:
200 mm
Teach in the current distance for “20 mA” in the menu
Operating example or steps:
RUN mode
→ Q
1
Output
/
to → Q
2
Output
→ Function Q
2
/Q
a
/
to → Teach Q
a
→ 4 mA
/
to → 20 mA
Position object
→ Saved
to → RUN mode
Necessary default settings:
Factory setting or function Q
2
/Q
a
=
4-20 mA
Mode Q
a
= Distance (only for user
level = Advanced)
Factory setting:
30,000 mm
6
OPERATION
52
O P E R A T I N G I N S T R U C T I O N S | DT50-2 Pro
8017154/1AVV/2021-03-24 | SICK