Operating Instructions
8 008 224/I982/08-00
CLV 41x Bar Code Scanner
Table 20 (contd)
Malfunction
11. AutoSetup:
CLV does not read the
presented, application-
specific bar code
(no acknowledgement from
beeper)
12. Profile programming
Possible cause
1. CLV not in AutoSetup mode
2. With profile programming: CLV
wait time of 5 s after power-up
exceeded
3. Profile programming: CLV wait
time of 10 s after presentation of
first profile bar code exceeded
4. Reading distance for presented
bar code incorrect
5. CLV is in total reflection
6. Bar code quality insufficient
1. CLV not in teach-in mode
2. CLV wait time of 5 s after power-
up exceeded
3. CLV wait time of 10 s after
presentation of first profile bar
code exceeded
Check
1. Is Dev. Rdy LED lit?
If so, the CLV is in Reading
mode again
2. See 1.
3. See 1.
4. Is reading distance for this
module width ok?
5. Is bar code presented at a
skew of less than 15° ?
6. See point 3.11 a, b, c
1. Is the Dev. Rdy LED lit?
If so, the CLV is in Reading
mode again
2. See 1.
3. See 1.
Remedy
1. User interface (after upload
from CLV): call A
UTO
S
ETUP
again in the V
IEW
menu
2. Switch CLV off and on again,
present profile bar code no.
10 within 5 s
3. As 2
4. Adjust reading distance. See
section
16. Reading field
diagrams
5. Rotate bar code accordingly,
see also
Section 9.1
6. See point 3.11 a, b, c
1. Switch CLV off and on again,
present required profile bar
code immediately (see also
Section 10.3
)
2. As 1.
3. As 1.
SICK service and repair
If correct operation of the CLV cannot be restored using the troubleshooting
measures provided above, the device may be defective. The CLV does not contain
any system components that can be repaired by the user.
Please contact the SICK Service department:
•
Through your local SICK subsidiary or branch office; the address and telephone
number are provided in the frame on the rear of these Operating Instructions
Please contact the SICK Service department first before sending in the device!
The CLV does not require maintenance. The self-monitoring functions enable the
device to operate fault-free at the reading station. The CLV indicates errors with the
status ST in the data output string (if enabled). If operated under extreme conditions
(excessive dust, abrasion, humidity), we recommended that you clean the reading
window at regular intervals using a mild, water-soluble detergent to maintain the
reading performance.
13. Maintenance
When cleaning the reading window, avoid any scratching or scouring movements
on the surface of the glass.
If necessary, also clean the LEDs.
CAUTION