O P E R AT I N G I N S T R U C T I O N S | C F P C U B I C
8021989 / 2017-10-20 | SICK AG
Subject to change without notice
4 2
10
OVERVIEW OF PARAMETERS
Parameter
Description
QaPol
The analog output signal can be inverted.
Normal = Analog output signal as configured.
Example: QaLow 4 mA/0 V and QAHigh 20 mA/10 V.
Invert = Analog output signal is inverted.
Example: QaLow 20 mA/10 V and QAHigh 4 mA/0 V.
QaHigh
Input of the fill level in mm/°C for 20 mA / 10 V signal
(QaHigh > QaLow).
QaLow
Input of the fill level in mm (inch)/°C (F) for 4 mA / 0 V
signal.
QaFail
Output behavior as per NE43 in the event of a fault (func-
tion only available when current output has been selected
under QaTyp).
3.5 mA = Analog current output is set to 3.5 mA in the
event of a fault.
21.5 mA = Analog current output is set to 21.5 mA in the
event of a fault.
SimQa
“8.5.9 Testing the configuration”.
Disp A/B
Display settings.
See:
“8.5.2 Setting an alternating display of measurands
UnitLv
Level display unit mm/inch.
UnitTm
Temperature display unit °C/°F.
SimLvl
“8.5.9 Testing the configuration”.
Setting the level to be simulated.
SimTmp
“8.5.9 Testing the configuration”.
Setting the temperature to be simulated.
Offset
Lock
“8.5.6 Locking the display with a password”.
AutoCal
Filter
“8.5.8 Filtering measured values”.
TrsHld
The factor which determines how strong a signal has to be
in order to be recognized by the device. The value range
lies between 20% and 500%.
The default is 100%. Only shown if password entered.
20% = high sensitivity
100% = standard
500% = low sensitivity
Adapt
“8.5.7 Setting the medium adjustment”.
CalEmp
Empty calibration.
See
Reset
Resetting the calibration for: empty adjustment, threshold,
and filter settings.
SigQa1
“8.5.10 Evaluating signal quality”.
SigQa2