O P E R AT I N G I N S T R U C T I O N S | C F P C U B I C
8021989 / 2017-10-20 | SICK AG
Subject to change without notice
3 4
8
OPERATION
Configuration
1.
Log in to Exprt mode, see
2.
Set the parameter to the desired fill level as a % in the
CONFIG / SIMLEV menu.
3. Activate the simulation.
•
Set the parameter to the required value in the QA-### / SIMQA menu.
Note:
The level simulation refers to the probe length and/or container level (probe
offset) if an offset is configured.
The simulation is only active when there are no error messages. The simulation is auto-
matically deactivated if the supply voltage is interrupted.
If Simulation mode is active during Run mode,
!SIMUL is displayed alternately with the
simulated values.
Parameter selection
−
SimOff: Off
−
Fill level 0%
−
Fill level 25%
−
Fill level 50%
−
Fill level 75%
−
Fill level 100%
8.5.10
Evaluating signal quality
The parameters describe the quality of the measuring signal and can be accessed
under EXPRT / INFO.
SigQu1
Characteristic for the robustness of the EXPRT / MEAS / TRSHLD setting.
•
Value range: 0 to 100%
•
Good signal: > 40%
Measures in the event of a poor signal: Reduce the value in the EXPRT / MEAS /
TRSHLD menu to increase SigQu1.
The EXPRT / MEAS / TRSHLD value must be set as high as possible so that no defec-
tive level is detected in the empty state.
SigQu2
Characteristic for the robustness of the medium detection in the event of interferences
(deposits/tank components).
•
Value range: 0 to 100%
•
Good signal: > 50%
A high characteristic describes a stable detection of the measuring medium. A low
characteristic indicates an unstable detection. In this case, a possible interference can
cause a stronger signal than the actual level and lead to faulty measurements.