The parameter P19 determines the duration of the test operation of the generator set.
If during the programming you change the value P18 the period count will restart from zero in
the moment in which you’ll exit the PROGRAMMING procedure.
The automatic periodical test is disabled if at least one of the two parameters is equal to zero
or if RTC based periodical test is enabled.
If RTC option is not installed it is possible to use only Standard mode periodical test procedure.
From 08.00.24 SW version and with RTC option installed it is possible to enable the function
of the Generator set on time and day bases.
This function let you prevent the start of the engine when emergency supply is not required;
otherwise you can use this function to start and stop the Generator set at needed time.
Three parameters are to be set to enable this function:
P70: time at which the operation in AUTO mode is enabled;
P71: time at which the operation in AUTO mode is disabled;
P72: days of the week when the operation is to be enabled;
P61: bit 4 to enable this function.
It is possible to configure only one set of enable time and one set of enable days.
If P70 is equal to P71 the Generator set will be enabled 24 hours at day but only during the
days enabled by P72.
When the system is in Time Lock, the display “V” and “A” together will show the message
“DISABL”.