20
User’s Manual
Disabling
Cannot be disabled
Conditions for its
activation
Key selector on AUTO or TEST
STOP button pressed o external STOP command
Filter time
0 seconds (immediate)
Visual signal
Message “F07” on the display “MULTIFUNCTION”
Disabling
Bit 5 of the Parameter P39 = 0
Conditions for its
activation
“FUEL END” digital input (terminal 06) shorted to ground
Filter time
20 seconds
Visual signal
Indicator “NO FUEL” slowly flashing
Disabling
Parameter P48 = 0 and/or parameter P28 = 0
Conditions for its
activation
Level detected from “FUEL LEVEL” (terminal 45) less or equal
than the threshold set by means parameter P28
Filter time
20 seconds
Visual signal
Indicator “NO FUEL” slowly flashing
Disabling
Bit 3 of the Parameter P39 = 0
Conditions for its
activation
No block
Engine running from the time set through the Parameter P31
Fuel solenoid activated
“OIL P. ALARM” digital input (terminal 07) shorted to ground
Filter time
2 seconds
Visual signal
Indicator “LOW OIL PRESSURE” slowly flashing
Disabling
Parameter P47 = 0 and/or parameter P34 = 0
Conditions for its
activation
No block
Engine running from the time set through the parameter P31
Fuel solenoid activated
Pressure detected from the “OIL PRESSURE” analogue input
(terminal 42) under or equal to the threshold set through the
parameter P34
Filter time
2 seconds
Visual signal
Indicator “LOW OIL PRESSURE” slowly flashing