User’s Manual    31

 

 

Normally, with the board in the MANUAL mode the users are switched on the mains. Only if 
the engine is running, if the generator is “present” and the delay before the supply has passed 
- P06 (or if the temperature exceeds the minimum threshold set with P55), the operator has 
the opportunity to switch them on the generator. To do that, press at the same time “MODE / 
ACK” and “F1” for one second (such combination is highlighted on the front panel of the board 
with the indication “MANUAL CHANGE-OVER”. This command works as “toggle”, that is, if 
the operator gives again the order the users are again switched on the mains.  

When  the  users  are  switched  on  the  generator  set,  they  are  automatically  switched  on  the 
mains if the generator gets “absent” or in presence of deactivations and/or blocks. 

 

The control sequence of the generator set in the AUTOMATIC mode develops as follows: 

1.  Start requests wait (typically mains failure) 

2.  Generator set starting attempts 

3.  Generator presence wait 

4.  Delay before supply the power 

5.  Switching users on the generator 

6.  No start requests wait 

7. 

Users’ switching on the mains 

8.  Engine cooling cycle 

9.  Engine shutdown cycle. 

 

 

In this phase the engine is dead. The board waits until the mains get “absent” or for at least 
one of the other start requests (see par.5.1.1).  

 

The board tries to start automatically the engine. The number of starting attempts to execute 
can be programmed through the parameter P10. If, after those attempts, the engine doesn’t 
start,  the  start  failure  block  is  activated  (“OVERCRANK”).  Furthermore,  the  duration  of  the 
starting  impulse  can  be  set  (parameter  P08)  as  well  as  the  delay  between  two  attempts 
(parameter P38). 

For each attempt the following operation are executed: 

1. 

The  “FUEL  SOLENOID”  output  (terminal  22)  is  enabled.  Such  output  is  automatically 
removed during shutdown cycles or when the engine is dead for 20 seconds. 

2.  Th

e “STOP SOLENOID” output (terminal 18), used for the excitation shutdown, is disabled 

(it should already be disabled unless the starting request occurs during a stop cycle). If 
the engine is already running, the procedure stops here. 

3.  If the preheat functio

n for diesel engines is enabled the “AUX OUTPUT 1” (terminal 15) is 

enabled  for  the  time  set with the  parameter  P20  (if  such  time  is  equal  to  0  the  preheat 
function is disabled). In this phase the display  “MULTIFUNCTION” shows the message 
“PRE”. At the end of this phase the output is disabled passing to phase 2. 

Summary of Contents for DST4600A

Page 1: ...Filename EAAM006212EN docx Rev 12 Date 30 05 2013 ID Document EAAM0062 Product DST4600A...

Page 2: ...rting Battery Fault 17 4 2 4 Minimum Fuel Level in the Tank 17 4 2 4 1 From Digital Input 17 4 2 4 2 From Analogue Input 17 4 2 5 Maximum Fuel Level in the Tank 17 4 2 5 1 From Digital Input 17 4 2 5...

Page 3: ...set Use 25 4 4 20 Engine not in thresholds when KG closed 25 5 Operating Sequence 26 5 1 Definitions 26 5 1 1 Mains Voltages Status 26 5 1 2 Generator s Voltages Status 27 5 1 3 Engine Status 28 5 1 3...

Page 4: ...ic Periodical Test 41 7 7 4 1 RTC based periodical test 41 7 7 4 2 Standard mode periodical test 41 7 7 5 Generator set Time Lock function 42 8 Differences between DST4600A and DST4600A P 43 8 1 1 ALA...

Page 5: ...code yy is the major version number and uu is the minor version number The complete SW identification number for the standard DST4600A is EB0220008yyuu reported in back panel as for example 8 00 22 Th...

Page 6: ...6 User s Manual DST4600A and DST4600A P front panels...

Page 7: ...ombined with the others can also take other meanings during some particular procedures not directly related with the management of the generator set programming calibration etc A button bearing the sy...

Page 8: ...explicit command of the operator if the generator is ready to supply of course In MAN the board will never execute such switching automatically When the selector is switched on MAN the engine keeps i...

Page 9: ...URS COUNT START COUNTER function Switch the key selector to OFF_RESET Press at the same time MODE ACK and STOP for 5 seconds After 5 seconds the counters will be reset The display does not indicate th...

Page 10: ...es field service maintenance F01 in presence of the deactivation for generator s voltage under the minimum threshold UNDERVOLTAGE F02 in presence of the block for generator s voltage over the maximum...

Page 11: ...e AUTOMATIC mode Turned on engine running Indicator GENERATOR LIVE green it indicates the status of the generator set It takes the following meanings Turned off the generator doesn t produce any volta...

Page 12: ...ays and the indicators L1 L2 L2 L3 and L3 L1 show the current phase However it is possible to force the display of one phase only even on three phase systems by pressing at the same time the buttons F...

Page 13: ...al input LOW LEVEL FUEL terminal 05 Analogue input FUEL LEVEL terminal 45 Indicator ALARM2 AUX ALARM red it indicates the masked generic block status It can be acquired from Digital input ALARM 2 term...

Page 14: ...sequences according to the position of the key selector During the operation of the generator set but even when it is not running some faults may occur The faults can be divided into three categories...

Page 15: ...if still active is disabled Once the operator has recognized the alarms they are automatically cancelled by DST4600A when the corresponding cause ceases to exist If the alarm is cancelled the visual s...

Page 16: ...hreshold set through the parameter P25 Fuel solenoid activated Filter time 2 seconds Visual signal Quick flashing of the indicator LOW OIL PRESSURE Disabling Bit 0 of the Parameter P39 0 Conditions fo...

Page 17: ...or parameter P33 0 Conditions for its activation Level detected from the analogue input FUEL LEVEL terminal 45 under or equal to the threshold set through the parameters P33 Filter time 2 seconds Vis...

Page 18: ...e load to Generator set keeping it running in case of F13 alarm Starting from revision 08 00 38 this block may be masked if mains is not present by using bit one of parameter P79 Disabling P75 0 Condi...

Page 19: ...ge F01 on the display MULTIFUNCTION Disabling Parameter P11 0 Conditions for its activation No deactivation No block Engine running Generator already in the window from starting Shutdown cycle not in...

Page 20: ...shold set by means parameter P28 Filter time 20 seconds Visual signal Indicator NO FUEL slowly flashing Disabling Bit 3 of the Parameter P39 0 Conditions for its activation No block Engine running fro...

Page 21: ...et through the parameter P35 Filter time 2 seconds Visual signal Indicator TEMPERATURE slowly flashing Disabling Bit 0 of the Parameter P49 0 Conditions for its activation No block ALARM 1 digital inp...

Page 22: ...nchronous engine version Filter time Time set through the parameter P23 Visual signal Message F04 on the display MULTIFUNCTION Disabling Bit 3 of the Parameter P49 0 and bit 1 of the parameter P61 0 C...

Page 23: ...r P16 at least on one phase Filter time 4 seconds if P76 is 0 otherwise the time depends on the amount of over current and on the value of P76 Visual signal Message F06 on the display MULTIFUNCTION St...

Page 24: ...ted The generator doesn t get in operating window for two seconds within the time limit set through the parameter P32 from the engine start Filter time Immediate Visual signal Message F08 on the displ...

Page 25: ...ctive power with negative sign and over the P52 threshold for the P53 time Filter time Immediate Visual signal Message F11 on the display MULTIFUNCTION Disabling Cannot be disabled Conditions for its...

Page 26: ...l input MAINS SIMULATION terminal 24 When such input is enabled the board wait for time T2 is elapsed before mains is considered present Furthermore if the board is set to work with an external mains...

Page 27: ...cy Hz P13 protection threshold for minimum generator s voltage Hz P14 protection threshold for maximum generator s voltage Hz Six thresholds are defined in the generator management Alive generator thr...

Page 28: ...nts is met Generator s frequency over the threshold specified through the parameter P42 only if enabled with bit 6 of the parameter P49 Voltage on all the generator s phases less than 80 V not configu...

Page 29: ...b Selector on AUTO or TEST and presence of a deactivation The control board can be set to work with engines equipped with an excitation shutdown system usually electromagnet with control on the engin...

Page 30: ...1 terminal15 for the time set with the parameter P20 if such time is equal to 0 the preheat function is disabled In this phase the display MULTIFUNCTION shows the message PRE At the end of this phase...

Page 31: ...gine cooling cycle 9 Engine shutdown cycle In this phase the engine is dead The board waits until the mains get absent or for at least one of the other start requests see par 5 1 1 The board tries to...

Page 32: ...from SW version 08 00 38 the activation sequence is subjected to the engine stopped or the shut down cycle completed conditions In this phase there s a wait until the generator reaches the operating s...

Page 33: ...is enabled bit 3 of P61 the solenoid is driven only for two seconds but the board waits in any case until P09 is elapsed At the end of the cycle if the engine is still running the shutdown failure blo...

Page 34: ...there s an energy inversion it is present on all the phases Further through the power factor some information on the type of load inductive or capacitive is given to the operator This information is p...

Page 35: ...ounter can be reset The reset procedure is the following one By pressing the F1 and F2 select the DATA HOURS COUNT START COUNTER function Switch the key selector to OFF_RESET Press at the same time MO...

Page 36: ...ration consists in setting the MAN mode manually make the mains supplying users and then set the AUTO mode again After these operations if the board doesn t acknowledge KR closed the alarm F13 is issu...

Page 37: ...ure the users are switched on the generator The following remote signals can be sent ENGINE RUNNING terminal 25 this output is enabled when the engine is running GENERAL ALARM terminal 26 this output...

Page 38: ...port of DST4600A board It is then possible to connect to this serial port one expansion board provided with 32 digital outputs or 16 outputs and 16 inputs The outputs can be used as additional remote...

Page 39: ...eactivated c If the supplied power value is in the range between P56 and P58 values OUTPUT 1 status is not changed from the actual status If INPUT A is deactivated KG open the procedure switches to st...

Page 40: ...let the watch running also without supply The expected duration of the battery is quite 10 years RTC has a full time date management set of function hours minutes seconds day month year and day of the...

Page 41: ...ill be stored pressing STOP the new values will be discarded In both cases the RTC setting mode is exited Remember to set the DAY OF WEEK value because it is required for a correct function of some fe...

Page 42: ...function of the Generator set on time and day bases This function let you prevent the start of the engine when emergency supply is not required otherwise you can use this function to start and stop th...

Page 43: ...ing test operation when the Generator set will be ready to supply This feature is valid for all type of test operation The operator can manually deactivate KG Boards with the new SW version use P66 an...

Page 44: ...e high water temperature alarm is disabled Only for this version the board can activate a block F40 when the KG is closed and the signal on terminal 10 becomes inactive with a fixed filter delay of 0...

Page 45: ...the right to modify this document without prior notice SICES has made any effort to ensure that the information herein provide are correct in any case SICES does not assume any liability for the use t...