24
Character
Name, Description, Setting Range
Factory Default
Alarm 4 hysteresis
1.0
• Sets Alarm 4 hysteresis.
• Not available if No alarm action is selected in [Alarm 4 type].
• Setting range:
Thermocouple, RTD input: 0.1 to 100.0
( )
DC voltage, current input: 1 to 1000 (The placement of the decimal point follows the
selection.)
Alarm 4 delay time
0 sec
• Sets Alarm 4 action delay time.
When the setting time has elapsed after the input enters the alarm output range, the
alarm is activated.
• Not available if No alarm action is selected in [Alarm 4 type].
• Setting range: 0 to 9999 seconds
Remote/Local
Local
• Selects Remote (Remote operation) or Local (keypad operation) setting of the SV.
• Available only when External setting input (EA option) is ordered.
•
: Local
: Remote
Remote bias
0
• Sets the remote bias value.
During remote action, the remote bias value is added to control desired value.
• Available only when External setting input (EA option) is ordered.
• Setting range:
20% of input span
External setting input high limit
1370
• Sets External setting input high limit value.
• Available only when External setting input (EA option) is ordered.
• Setting range: External setting input low limit to Scaling high limit
External setting input low limit
–200
• Sets External setting input low limit value.
• Available only when External setting input (EA option) is ordered.
• Setting range: Scaling low limit to External setting input high limit
SV Rise/Fall rate start type
SV start
• Selects SV or PV start for the SV ramp function.
•
: SV start
: PV start
SV rise rate
0
/minute
• Sets SV rise rate (rising value for 1 minute).
• Setting to 0 (zero) disables this function.
• Setting range: 0 to 9999
/min ( /min) (The placement of the decimal point follows
the selection.)
Thermocouple, RTD input: 0.0 to 999.9
/min ( /min)
DC voltage, current input: 0 to 9999/min
SV fall rate
0
/minute
• Sets SV fall rate (falling value for 1 minute).
• Setting to 0 (zero) disables this function.
• Setting range: 0 to 9999
/min ( /min) (The placement of the decimal point follows
the selection.)
Thermocouple, RTD input: 0.0 to 999.9
/min ( /min)
DC voltage, current input: 0 to 9999/min