43
Set value memory external selection (EI option)
Switches SV1 and SV2 by external contact.
If 001 is selected in [Event input DI allocation]:
DI input Open: SV1
DI input Closed: SV2
If 008 is selected in [Event input DI allocation]:
DI input Open: SV2
DI input Closed: SV1
Circuit current when closed: Approx. 2 mA
External setting input (EA option)
If
‘
Remote
’
is selected in [Remote/Local], external analog signal will become SV.
Remote bias value is added to the control desired value.
Setting signal:
Direct current 4 to 20 mA
Allowable input:
50 mA DC max.
Input impedance:
50
max.
Input sampling period: 125 msec
Option combination
( : Can be used together.)
Option Code
W
DC
C5
EA
EI
W
-
-
DC
C5
EA
-
-
EI
-
-
W, EA and EI options cannot be used together.