25
Character
Name, Description, Setting Range
Factory Default
Control output OUT1/EVT
OUT1
• OUT1 or EVT terminals can be selected for control output OUT1.
If OUT1 is selected, the output terminals will be as follows.
Control output OUT1: O1 terminals (
③
-
④
)
Event output:
EV terminals (
⑧
-
⑨
)
If EVT is selected, output terminals will be as follows.
Control output OUT1: EV terminals (
⑧
-
⑨
)
Event output:
O1 terminals (
③
-
④
)
Select
(EVT) if control output OUT1 is used as Open collector output.
• Not available for direct current output.
•
: OUT1
: EVT
Heater burnout alarm output Enabled/Disabled
Enabled
• Selects whether EVT output is used for Heater burnout alarm output.
If Heater burnout alarm, Loop break alarm and Alarm (1- 4) output are set to
“Enabled”, they utilize common output terminals.
• Available only when Heater burnout alarm (W option) is ordered.
•
: Disabled
: Enabled
Loop break alarm output Enabled/Disabled
Enabled
• Selects whether EVT output is used for Loop break alarm output.
If Loop break alarm, Heater burnout alarm and Alarm (1 - 4) output are set to
“Enabled”, they utilize common output terminals.
• Available only when Heating/Cooling control (DC option) is ordered.
•
: Disabled,
: Enabled
Alarm 1 output Enabled/Disabled
Enabled
• Selects whether EVT output is used for Alarm 1 output.
If Loop break alarm, Heater burnout alarm, Alarm 2, Alarm 3 and Alarm 4 output are
set to “Enabled”, they utilize common output terminals.
• Not available if Heating/Cooling control (DC option) is ordered.
•
: Disabled
: Enabled
Alarm 2 output Enabled/Disabled
Disabled
• Selects whether EVT output is used for Alarm 2 output.
If Loop break alarm, Heater burnout alarm, Alarm 1, Alarm 3 and Alarm 4 output are
set to “Enabled”, they utilize common output terminals.
• Not available if Heating/Cooling control (DC option) is ordered.
•
: Disabled
: Enabled
Alarm 3 output Enabled/Disabled
Disabled
• Selects whether EVT output is used for Alarm 3 output.
If Loop break alarm, Heater burnout alarm, Alarm 1, Alarm 2 and Alarm 4 output are
set to “Enabled”, they utilize common output terminals.
• Not available if Heating/Cooling control (DC option) is ordered.
•
: Disabled
: Enabled