50
11. Troubleshooting
If any malfunctions occur, check if the power is supplied to the PLC, CIT-200 and C series. If the power is
supplied to them, a green power indicator (POWER) lights up.
Check the following and C series “12. Troubleshooting” when they do not work even if the indicator lights up.
Warning
Turn the power supplied to the instrument OFF before wiring or checking.
Working with the power switched ON may result in severe injury or death due to
Electric Shock.
n
Problem: Communication is impossible.
Presumed cause
Solution
• The disconnection of communication cable or
imperfect contact between the cable and terminal
Change the cable, or fasten the screw of
the terminal securely.
• Setup of the CIT-200 is mistaken.
Refer to pages 9 and 10.
• Setup of the CPT-20A is mistaken.
Refer to pages 9 and 10.
• The wiring of communication cable is not correct.
Wire it properly. (pp.13 to 17)
• Setup of the PLC is not correct.
Setup of Mitsubishi PLC: pp. 17 to 19
Setup of Omron PLC : pp. 34
Setup of Fuji PLC
: pp. 41
• Initial setting of the PLC is not correct.
Initial setting of Mitsubishi PLC : pp. 20
Initial setting of Omron PLC
: pp. 34 to 40
Initial setting of Fuji PLC
: pp. 42 to 47
• When using the communication line RS-422A,
terminators are not connected at the end of the
PLC unit.
Connect terminators, referring to the instruction
manual for each PLC.
If any unexplained malfunctions occur other than the above mentioned, make inquiries at our agency or
the shop where you purchased the unit.