38
DM1009 to
DM1019
For future extension
DM1020 to
DM1119
Main setting value (SV) setting
Main setting value from Ch1 to Ch100
Setting range: Refer to the
Instruction manual for C series “11.2
Temperature control unit (CCT-235)”.
DM1120 to
DM1219
Main proportional band setting
Main proportional band from Ch1 to
Ch100
Setting range: 0.0 to 100.0%
DM1220 to
DM1319
Integral time setting
Integral time from Ch1 to Ch100
Setting range: 0 to 3600 seconds
DM1320 to
DM1419
Derivative time setting
Derivative time from Ch1 to Ch100
Setting range: 0 to 3600 seconds
DM1420 to
DM1519
Alarm 1 (high limit) setting
Alarm 1 (high limit) setting value from
Ch1 to Ch100
Setting range: Refer to the
Instruction manual for C series “11.2
Temperature control unit (CCT-235)”.
DM1520 to
DM1619
Alarm 2 (low limit) setting
Alarm 2 (low limit) setting value from
Ch1 to Ch100
Setting range: Refer to the
Instruction manual for C series “11.2
Temperature control unit (CCT-235)”.
DM1620 to
DM1719
Main proportional cycle setting
Main proportional cycle from Ch1 to
Ch100
Setting range: 1 to 120 seconds
DM1720 to
DM1819
Heater burnout alarm setting
Heater burnout alarm value from Ch1
to Ch100
Setting range: 0.0 to 20.0A [W(20A)]
0.0 to 50.0A [W(50A)]
DM1820 to
DM1919
Control action Perform/Stop
Control action Perform/Stop from
Ch1 to Ch100
0: Control Stop 1: Control Perform
DM1920 to
DM2019
Auto-tuning Perform/Cancel
Auto-tuning Perform/Cancel from
Ch1 to Ch100
0: AT Cancel 1: AT Perform
DM2020 to
DM2119
Alarm 1 (high limit) hysteresis setting
Alarm 1 (high limit) hysteresis from
Ch1 to Ch100
Setting range:
0.1 to 100.0 (Thermocouple, RTD)
1 to 1000 (DC current, voltage)
DM2120 to
DM2219
Alarm 2 (low limit) hysteresis setting
Alarm 2 (low limit) hysteresis from
Ch1 to Ch100
Setting range:
0.1 to 100.0 (Thermocouple, RTD)
1 to 1000 (DC current, voltage)
DM2220 to
DM2319
Control output ON/OFF action hysteresis
setting
Control output ON/OFF action
hysteresis from Ch1 to Ch100
Setting range:
0.1 to 100.0 (Thermocouple, RTD)
1 to 1000 (DC current, voltage)
DM2320 to
DM2419
Control output high limit setting
Control output high limit value from
Ch1 to Ch100
Setting range: Control output low
limit value to 105%
DM2420 to
DM2519
Control output low limit setting
Control output low limit value from
Ch1 to Ch100
Setting range: -5% to Control output
high limit value