24
Address
Contents
Setting range, information
R1000
Sets the number of CPT-20A units
connected to the CIT-200 to every 4-bit of
word data.
(0 is regarded as 1 unit.)
(e.g.) 5 CPT-20A units are connected: 0005H
16
0
: The number of the CPT-20A
16
1
: Ignored
16
2
: Ignored
16
3
: Ignored
Setting range: 1 to 10H
R1001
Sets the number of CCT-235 units
connected to the CPT-20A to every 4-bit of
word data.
(0 is regarded as 1 unit.)
(e.g.) 10 CCT-235 units are connected to
4 CPT-20A units (instrument No.0
to No.3): AAAAH
16
0
: Instrument No. 0 CPT-20A
16
1
: Instrument No. 1 CPT-20A
16
2
: Instrument No. 2 CPT-20A
16
3
: Instrument No. 3 CPT-20A
Setting range: 1 to AH
R1002
Sets the number of CCT-235 units
connected to the CPT-20A to every 4-bit of
word data.
(0 is regarded as 1 unit.)
(e.g.) 10 CCT-235 units are connected to
instrument No.4 CPT-20A unit: 000AH
16
0
: Instrument No. 4 CPT-20A
16
1
: Instrument No. 5 CPT-20A
16
2
: Instrument No. 6 CPT-20A
16
3
: Instrument No. 7 CPT-20A
Setting range: 1 to AH
R1003
Sets the number of CCT-235 units
connected to the CPT-20A to every 4-bit of
word data.
(0 is regarded as 1 unit.)
(e.g.) CPT-20A is not connected: 0000H
16
0
: Instrument No. 8 CPT-20A
16
1
: Instrument No. 9 CPT-20A
16
2
: Instrument No. 10 CPT-20A
16
3
: Instrument No. 11 CPT-20A
Setting range: 1 to AH
R1004
Sets the number of CCT-235 units
connected to the CPT-20A to every 4-bit of
word data.
(0 is regarded as 1 unit.)
(e.g.) CPT-20A is not connected: 0000H
16
0
: Instrument No. 12 CPT-20A
16
1
: Instrument No. 13 CPT-20A
16
2
: Instrument No. 14 CPT-20A
16
3
: Instrument No. 15 CPT-20A
Setting range: 1 to AH
R1005 Designates
Communication item Used/
Not used selection flag for every 1 bit of
word data.
1: Used 0: Not used
2
0
: Main setting value
2
1
: Main proportional band
2
2
: Integral time
2
3
: Derivative time
2
4
: Alarm 1 (high limit) setting
2
5
: Alarm 2 (low limit) setting
2
6
: Main proportional cycle
2
7
: Heater burnout alarm
2
8
: Control action Perform/Stop
2
9
: Auto-tuning Perform/Cancel
2
10
: Alarm 1 (high limit) hysteresis
2
11
: Alarm 2 (low limit) hysteresis
2
12
: Control output ON/OFF action
hysteresis
2
13
: Control output high limit
2
14
: Control output low limit
2
15
: PV (input) filter
R1006 Designates
Communication item Used/
Not used selection flag for every 1 bit of
word data.
1: Used 0: Not used
2
0
: Temperature unit
2
1
: Control action (Heating/Cooling)
2
2
: Alarm 1 action
2
3
: Alarm 2 action
2
4
: Loop break alarm 1 action span
2
5
: Loop break alarm 1 action time
2
6
: Anti-reset windup
2
7
: PD (Manual) reset
2
8
: Sensor correction
2
9
: Loop break alarm 2 action span
2
10
: Loop break alarm 2 action time
2
11
: Cooling proportional band
2
12
: Cooling proportional cycle
2
13
: Overlap band/Dead band
2
14
: Cooling action mode
2
15
: Cooling output ON/OFF action
hysteresis