W30.2620 to
W30.2719
Temperature unit setting
Temperature unit from Ch1 to Ch100
0:
1:
W30.2720 to
W30.2819
Control action setting
Control action from Ch1 to Ch100
0: Heating action 1: Cooling action
W30.2820 to
W30.2919
Alarm 1 action selection
Alarm 1 action from Ch1 to Ch100
0: No alarm action
1: High limit alarm
2: High limit alarm with standby
3: Low limit alarm
4: Low limit alarm with standby
5: H/L limits alarm
6: H/L limits alarm with standby
7: H/L limit range alarm
8: H/L limit range alarm with standby
9: Process high alarm
10: Process high alarm with standby
11: Process low alarm
12: Process low alarm with standby
W30.2920 to
W30.3019
Alarm 2 action selection
Alarm 2 action from Ch1 to Ch100
The selection items are the same as
those of Alarm 1 action
W30.3020 to
W30.3119
Loop break alarm 1 action span setting
Loop break alarm 1 action span from
Ch1 to Ch100
Setting range:
0.0 to 100.0 (Thermocouple, RTD)
1 to 1000 (DC current, voltage)
W30.3120 to
W30.3219
Loop break alarm 1 action time setting
Loop break alarm 1 action time from
Ch1 to Ch100
Setting range: 200 minutes
W30.3220 to
W30.3319
Anti-reset windup setting
Anti-reset windup from Ch1 to Ch100
Setting range: 0 to 100%
W30.3320 to
W30.3419
PD (Manual) reset setting
PD (Manual) reset value from Ch1 to
Ch100
Setting range: Proportional band
converted value, however, within
the range of -199.9 to 999.9
W30.3420 to
W30.3519
Sensor correction setting
Sensor correction value from Ch1 to
Ch100
Setting range:
-100.0 to 100.0 (Thermocouple,
RTD)
-1000 to 1000 (DC current, voltage)
W30.3520 to
W30.3619
Loop break alarm 2 action span setting
Loop break alarm 2 action span from
Ch1 to Ch100
Setting range:
0.0 to 100.0 (Thermocouple, RTD)
1 to 1000 (DC current, voltage)
W30.3620 to
W30.3719
Loop break alarm 2 action time setting
Loop break alarm 2 action time from
Ch1 to Ch100
Setting range: 200 minutes
W30.3720 to
W30.3819
Cooling proportional band setting
Cooling proportional band from Ch1
to Ch100
Setting range: Multiplying factor to
Heating proportional band
0.0 to 10.0 (ON/OFF action when set
to 0.0)
W30.3820 to
W30.3919
Cooling proportional cycle setting
Cooling proportional cycle from Ch1
to Ch100
Setting range: 1 to 120 seconds