To enter the Program pattern group, follow the procedure below.
(1)
Press the
key in PV/SV Display Mode.
The unit proceeds to the Program pattern group.
(2)
Press the
key.
The unit proceeds to ‘Step 1 SV’.
Character
Setting Item, Function, Setting Range
Factory Default
Step 1 SV
0
• Sets Step 1 SV.
• Setting range: Scaling low limit value to Scaling high limit value
Step 1 time
00:00
• Sets Step 1 time.
• Setting range: 00:00 to 99:59
Step 1 wait value
0
• Sets Step 1 wait value.
This function prevents the step from proceeding to the next one until
PV enters the range of SV Wait value regardless of the step time.
Setting the value to 0 or 0.0 disables this function.
• Setting range: 0 to Converted value of 20% of input span
Step 1 EVT1 alarm value
0
• Sets Step1 EVT1 alarm value.
If the independent alarm (High/Low limits independent, High/Low limit
range independent, or High/Low limits with standby independent) is
selected in [Event output EVT1 allocation], the EVT1 alarm value
matches the EVT1 low limit alarm value.
Setting the value to 0 or 0.0 disables this alarm (except Process
high and Process low alarm).
Not available if No event is selected in [Event output EVT1 allocation].
Available when the Alarm output is selected in [Event output EVT1
allocation].
• Setting range: Refer to (Table 7.1.2-1) on p. 55.
Step 1 EVT1 high limit alarm value
0
• Sets Step 1 EVT1
high limit alarm value.
Setting the value to 0 or 0.0 disables this alarm (except Process
high and Process low alarm)
.
Available when the independent alarm (High/Low limits independent,
High/Low limit range independent, or High/Low limits with standby
independent) is selected in [Event output EVT1 allocation].
• Setting range: Refer to (Table 7.1.2-1) on p. 55.