SV
OUT2 proportional band
Air cooling
Oil cooling
Water cooling
Character
Setting Item, Function, Setting Range
Factory Default
OUT2 cooling method
Air cooling
• Selects OUT2 cooling method from air, oil or water cooling.
Available when the D option is ordered.
Not available if OUT2 is in ON/OFF control.
•
: Air cooling (linear characteristics)
: Oil cooling (1.5th power of the
linear characteristics)
: Water cooling (2nd power of the
linear characteristics)
(Fig. 6.3.2-1)
OUT2 high limit
100%
• Sets OUT2 high limit value.
Available if the D option is ordered.
Not available if OUT2 is in ON/OFF control.
• Setting range: OUT2 low limit value to 100%
(Direct current output type: OUT2 low limit value to 105%)
OUT2 low limit
0%
• Sets OUT2 low limit value.
Available if the D option is ordered.
Not available if OUT2 is in ON/OFF control.
• Setting range: 0% to OUT2 high limit value
(Direct current output type: -5% to OUT2 high limit value)
Overlap band/Dead band
0.0
• Sets the overlap band or dead band for OUT1 and OUT2.
+ Set value: Dead band, –Set value: Overlap band
Available only when the D option is ordered
• Setting range: -200.0 to 200.0 ( ),
DC voltage, current inputs: -2000 to 2000 (The placement of the
decimal point follows the selection.)
OUT2 ON/OFF hysteresis
1.0
• Sets OUT2 ON/OFF hysteresis.
Available when the D option is ordered.
Available when OUT2 is in ON/OFF control action.
• Setting range: 0.1 to 1000.0 ( ),
DC voltage, current inputs: 1 to 10000 (The placement of the decimal
point follows the selection.)
Direct/Reverse action
Reverse (Heating) action
• Selects either Reverse (Heating) or Direct (Cooling) control action.
•
: Reverse (Heating)
action
: Direct (Cooling) action