![Shinko ACD-13A Instruction Manual Download Page 27](http://html.mh-extra.com/html/shinko/acd-13a/acd-13a_instruction-manual_1258167027.webp)
- 27 -
Character
Setting Item, Function, Setting Range
Factory Default
J
-328 to
1832
R
32 to
3200
S
32 to
3200
B
32 to
3308
E
-328 to
1472
T
-328.0 to
752.0
N
-328 to
2372
PL-
32 to
2534
C(W/Re5-26)
32 to
4199
Pt100
-328.0 to 1562.0
JPt100
-328.0 to
932.0
Pt100
-328 to
1562
JPt100
-328 to
932
Pt100
-148.0 to
212.0
Pt100
-148.0 to
932.0
4 to 20 mA DC
-2000 to 10000
0 to 20 mA DC
-2000 to 10000
0 to 10 mV DC
-2000 to 10000
-10 to 10 mV DC -2000 to 10000
0 to 50 mV DC
-2000 to 10000
0 to 100 mV DC -2000 to 10000
0 to 1 V DC
-2000 to 10000
0 to 5 V DC
-2000 to 10000
1 to 5 V DC
-2000 to 10000
0 to 10 V DC
-2000 to 10000
Scaling high limit (*)
1370
• Sets scaling high limit value.
• Setting range: Scaling low limit value to input range high limit value
DC voltage, current inputs: -2000 to 10000 (The placement of the
decimal point follows the selection.)
Scaling low limit (*)
-200
• Sets scaling low limit value.
• Setting range: Input range low limit value to scaling high limit value
DC voltage, current inputs: -2000 to 10000 (The placement of the
decimal point follows the selection.)
(*)
In the case of DC voltage, current inputs, if Scaling high limit value< Scaling low limit
value is set, PV scaling decrease/input increase is possible.