Heater burnout alarm output setting items:
When ‘Heater burnout alarm output’ is
selected in [Event output allocation].
Character
Setting Item, Setting Range
Data
Heater rated current
: 20.0 A
: 100.0 A
Heater burnout alarm 1 value
Rated current 20.0 A: 0.0 to 20.0 A,
100.0 A: 0.0 to 100.0 A
Heater burnout alarm 2 value
Rated current 20.0 A: 0.0 to 20.0 A,
100.0 A: 0.0 to 100.0 A
Loop break alarm setting items:
When ‘Loop break alarm output’ is selected in [Event
output allocation].
Character
Setting Item, Setting Range
Data
Loop break alarm time
0 to 200 minutes
Loop break alarm band
0 to 150 ( ) or 0.0 to 150.0 ( )
DC voltage, current inputs: 0 to 1500 (The placement
of the decimal point follows the selection.)
Time signal output setting items:
When ‘Time signal output’ is selected in [Event
output allocation]
Character
Setting Item, Setting Range
Data
Time signal output step
Setting range: 1 to 15
Time signal output OFF time
Setting range: 00:00 to 99:59
(Time unit follows the selection in [Step time unit] in
the Program group)
Time signal output ON time
Setting range: 00:00 to 99:59
(Time unit follows the selection in [Step time unit] in
the Program group)