- 116 -
OUT1 MV preset output
Setting range: 0.0 to 100.0%
(Direct current output: -5.0 to 105.0%)
OUT2 MV preset output
Setting range: 0.0 to 100.0%
(Direct current output: -5.0 to 105.0%)
Event input group
Character
Setting Item, Setting Range
Data
Event input group
Event input EVI1 allocation
Refer to Event Input Allocation Table.
Event input EVI2 allocation
Refer to Event Input Allocation Table.
Event input EVI3 allocation
Refer to Event Input Allocation Table.
Event input EVI4 allocation
Refer to Event Input Allocation Table.
Event Input Allocation Table
Selected
value
Event input function
Input ON
(Closed)
Input OFF
(Open)
Remarks
000
No event
001
Set value memory
2
n
1
n=0 to 3
002
Control ON/OFF
Control OFF Control ON
Control output
OFF function
003
Direct/Reverse action
Direct
action
Reverse
action
Always effective
004
Timer Start/Stop
Start
Stop
005
PV Display;
PV holding
Holding
Not holding
Ineffective when
controlling
006
PV Display;
PV peak value holding
Holding
Not holding
Ineffective when
controlling
007
Preset output 1
Preset
output
Standard
control
If sensor is burnt
out, the unit
maintains control
with the preset
output MV.