Shinko ACD-13A Instruction Manual Download Page 107

-  107  - 

Character 

Setting Item, Setting Range 

Data 

 

Step 4 EVT5 high limit alarm value 

 

 

Step 5 SV 

 

 

Step 5 time 

 

 

Step 5 Wait value 

 

 

Step 5 EVT1 alarm value 

 

 

Step 5 EVT1 high limit alarm value 

 

 

Step 5 EVT2 alarm value 

 

 

Step 5 EVT2 high limit alarm value 

 

 

Step 5 EVT3 alarm value 

 

 

Step 5 EVT3 high limit alarm value 

 

 

Step 5 EVT4 alarm value 

 

 

Step 5 EVT4 high limit alarm value 

 

 

Step 5 EVT5 alarm value 

 

 

Step 5 EVT5 high limit alarm value 

 

 

Step 6 SV 

 

 

Step 6 time 

 

 

Step 6 Wait value 

 

 

Step 6 EVT1 alarm value 

 

 

Step 6 EVT1 high limit alarm value 

 

 

Step 6 EVT2 alarm value 

 

 

Step 6 EVT2 high limit alarm value 

 

 

Step 6 EVT3 alarm value 

 

 

Step 6 EVT3 high limit alarm value 

 

 

Step 6 EVT4 alarm value 

 

 

Step 6 EVT4 high limit alarm value 

 

 

Step 6 EVT5 alarm value 

 

 

Step 6 EVT5 high limit alarm value 

 

 

Step 7 SV 

 

 

Step 7 time 

 

 

Step 7 Wait value 

 

 

Step 7 EVT1 alarm value 

 

 

Step 7 EVT1 high limit alarm value 

 

 

Step 7 EVT2 alarm value 

 

 

Step 7 EVT2 high limit alarm value 

 

 

Step 7 EVT3 alarm value 

 

 

Step 7 EVT3 high limit alarm value 

 

 

Step 7 EVT4 alarm value 

 

 

Step 7 EVT4 high limit alarm value 

 

 

Step 7 EVT5 alarm value 

 

 

Step 7 EVT5 high limit alarm value 

 

 

Step 8 SV 

 

Summary of Contents for ACD-13A

Page 1: ...DIGITAL INDICATING CONTROLLERS ACD 13A ACR 13A INSTRUCTION MANUAL ...

Page 2: ...t an electrical shock or fire only Shinko or other qualified service personnel may handle the inner assembly To prevent an electrical shock fire or damage to the instrument parts replacement may only be undertaken by Shinko or other qualified service personnel Safety Precautions To ensure safe and correct use thoroughly read and understand this manual before using this instrument This instrument i...

Page 3: ...inal with an insulation sleeve in which the M3 screw fits when wiring the instrument The terminal block of this instrument is designed to be wired from the left side The lead wire must be inserted from the left side of the terminal and fastened with the terminal screw Tighten the terminal screw using the specified torque If excessive force is applied to the screw when tightening the terminal screw...

Page 4: ...evere injury or death due to electrical shock Use a soft dry cloth when cleaning the instrument Alcohol based substances may tarnish or deface the unit As the display section is vulnerable be careful not to put pressure on scratch or strike it with a hard object Abbreviations used in this manual Abbreviation Term PV Process variable SV Desired value MV Output manipulated variable DV Deviation AT A...

Page 5: ...Event Output Group 34 6 3 5 Program Group 42 6 3 6 Communication Group 43 6 3 7 External Setting Group 45 6 3 8 Transmission Output Group 46 6 3 9 Other Function Group 47 7 Settings 52 7 1 Simplified Setting Method 52 7 1 1 SV Setting Mode 52 7 1 2 Event Setting Mode 52 7 1 3 PID Setting Mode 56 7 2 Group Selection 58 7 2 1 SV Event Group for Fixed Value Control 58 7 2 2 Program Pattern Group for ...

Page 6: ...Setting Overlap Band 88 12 Specifications 89 12 1 Standard Specifications 89 12 2 Optional Specifications 95 13 Troubleshooting 99 13 1 Indication 99 13 2 Key Operation 100 13 3 Control 101 14 Character Tables 102 15 Operation Flowchart 127 15 1 Simplified Setting SV Event PID Setting Modes For Fixed Value Control Only 127 15 2 Group Selection for Fixed Value Control 128 15 3 Group Selection for P...

Page 7: ...oltage for SSR drive 12 V DC 15 DA Direct current 4 to 20 mA DC C RS 232C Serial communication C5 RS 485 EA1 4 to 20 mA DC External setting input EA2 0 to 20 mA DC EV1 0 to 1 V DC EV2 1 to 5 V DC TA1 4 to 20 mA DC Transmission output TV1 0 to 1 V DC P Insulated power output 1 13 types of alarm action including No event and Energized De energized Timer output Heater burnout alarm output option Loop...

Page 8: ... the case ACD 13A Model Power supply voltage 1 is entered for 24 V AC DC option Serial number e g Relay contact output Multi range input Fig 1 2 1 ACR 13A Model Power supply voltage 1 is entered for 24 V AC DC option Serial number e g Relay contact output Multi range input Fig 1 2 2 ...

Page 9: ... 9 2 Name and Functions ACD 13A ACR 13A Fig 2 1 1 2 3 4 5 7 8 10 11 12 13 6 8 14 15 17 17 6 1 2 3 4 5 16 9 7 10 9 14 15 16 11 12 13 ...

Page 10: ... Set value memory number or step number program control 9 M S indicator M Lights when step time unit Hours Minutes is selected in the program control S Lights when step time unit Minutes Seconds is selected in the program control 10 Action indicators OUT1 Lights when control output OUT1 is ON For direct current output type flashes corresponding to the MV in 125 ms cycles OUT2 Lights when control o...

Page 11: ...witched by pressing this key for 1 second In standby mode pressing this key turns all outputs OFF as when the power supply is turned off In program mode control RUNS STOPS In standby mode pressing this key RUNS program control Program control STOPS by pressing this key for 1 second during program operation RUN 16 A M B MODE key Switches Auto Manual control If this key is pressed during setting mod...

Page 12: ... 104 5 When terminal cover is used 91 106 2 3 Mounting to the Control Panel 3 1 External Dimensions Scale mm ACD 13A Fig 3 1 1 ACR 13A Fig 3 1 2 Gasket Screw type mounting bracket Terminal cover Sold separately Gasket Screw type mounting bracket Terminal cover Sold separately ...

Page 13: ...cation Drip proof Dust proof may be compromised and all warranties will be invalidated ACD 13A Horizontal close mounting n Number of mounted units Fig 3 2 1 ACR 13A Horizontal close mounting n Number of mounted units Fig 3 2 2 130 92 0 8 0 45 0 5 0 n x 48 3 0 5 0 92 0 8 0 92 0 8 0 130 n 96 3 0 5 0 92 0 8 0 ...

Page 14: ...t the unit Mount the controller vertically to the flat rigid panel to ensure it adheres to the Drip proof Dust proof specification IP66 Mountable panel thickness 1 to 8 mm 1 Insert the controller from the front side of the panel 2 Attach the mounting brackets by the holes at the top and bottom of the case and secure the controller in place with the screws How to remove the unit 1 Turn the power to...

Page 15: ... Terminal Use a solderless terminal with an insulation sleeve in which an M3 screw fits as shown below The torque should be 0 63 N m Solderless Terminal Manufacturer Model Tightening Torque Y type Nichifu Terminal Industries CO LTD TMEV1 25Y 3 0 63 N m Japan Solderless Terminal MFG CO LTD VD1 25 B3A Ring type Nichifu Terminal Industries CO LTD TMEV1 25 3 Japan Solderless Terminal MFG CO LTD V1 25 ...

Page 16: ...7 8 DA Direct current 9 10 7 8 DS Non contact voltage 9 10 7 8 DR Relay contact 9 10 A3 Event output EVT1 to EVT3 7 8 9 10 EVT3 EVT1 EVT2 7 8 9 10 EVT2 EVT1 16 17 18 19 20 DC V DC voltage 0 to 5 V 1 to 5 V 0 to 10 V 16 17 18 19 20 DC A Direct current 4 to 20 mA 0 to 20 mA 16 17 18 19 20 RTD A B B 16 17 18 19 20 TC Thermocouple Input Option Option Option 11 12 13 14 15 DI2 DI4 DI3 DI1 EI Event inpu...

Page 17: ... output EVT1 to EVT3 7 8 9 10 EVT3 EVT1 EVT2 7 8 9 10 EVT2 EVT1 16 17 18 19 20 DC V DC voltage 0 to 5 V 1 to 5 V 0 to 10 V 16 17 18 19 20 DC V DC voltage 0 to 10 mV 10 to 10 mV 0 to 50 mV 0 to 100 mV 0 to 1 V 16 17 18 19 20 RTD A B B Input Option Option Option 11 12 13 14 15 DI2 DI4 DI3 DI1 EI Event input 16 17 18 19 20 TC Thermocouple 16 17 18 19 20 DC A Direct current 4 to 20 mA 0 to 20 mA Event...

Page 18: ...ple ACD 13A R M To prevent the unit from harmful effects of unexpected high level noise it is recommended that a surge absorber be installed between the electromagnetic switch coils ACD 13A S M 1 W Number of Shinko SSR units when connected in parallel SA 400 series 5 units SA 500 series 2 units For a 24 V AC DC of power source do not confuse polarity when using a direct current DC Fig 4 3 1 Fig 4 ...

Page 19: ...for detecting current under phase control 2 Use the current transformer CT provided and pass one lead wire of heater circuit into the hole of the CT 3 When wiring keep CT wire away from AC sources and load wires to avoid the external interference Single phase heater Fig 4 3 3 Three phase heater Fig 4 3 4 25 26 25 26 27 ...

Page 20: ...p Each setting item Same as the above Communication group 5 Each setting item Same as the above External setting group 5 Each setting item Same as the above Transmission output group 5 Each setting item Same as the above Other function group Each setting item Same as the above From 2 Simplified setting Group selection 3 sec 2 1sec 3 sec 1sec 1sec 1sec 1sec 1sec 1sec 1sec 1sec 1sec 1sec 1sec 1sec I...

Page 21: ... Settings pp 52 68 Factory default of the Engineering group Input group pp 26 28 Setting Item Factory Default Input type K 200 to 1370 Scaling high limit 1370 Scaling low limit 200 Decimal point place No decimal point PV filter time constant 0 0 seconds Sensor correction 0 0 Output group pp 29 31 Setting Item Factory Default OUT1 proportional cycle Relay contact output 30 seconds Non contact volta...

Page 22: ...ent output EVT5 allocation A5 option No event Program group p 42 Setting Item Factory Default Fixed value control Program control Fixed value control Step time unit Hours Minutes Power restore action Stops after power is restored Program start temperature 0 Communication group C or C5 option pp 43 44 Setting Item Factory Default Communication protocol Shinko protocol Instrument number 0 Communicat...

Page 23: ...ansmission output low limit 200 Other function group pages 47 51 Setting Item Factory Default Set value lock Unlock PID zone function Not used SV rise rate 0 minute SV fall rate 0 minute Indication when output OFF OFF indication Backlight selection All are backlit PV color Red PV color range 5 0 Backlight time 0 minutes Bar graph MV indication Deviation unit 1 ...

Page 24: ...status Control will then start indicating the PV on the PV Display and SV on the SV MV TIME Display While the control output OFF function is working the PV Display indicates Indication differs depending on the selection in Indication when output OFF Table 6 1 1 Sensor Input PV Display SV MV TIME Display PV Display SV MV TIME Display K J R S B E T N PL C W Re5 26 Pt100 JPt100 Pt100 JPt100 Pt100 Pt1...

Page 25: ...nit proceeds to the next setting item If the key is pressed at the last setting item the unit proceeds to the first setting item Pressing the key reverts to the previous setting item Pressing the key for 1 second reverts to the previous setting level reverts from setting item to each group If the key is pressed for 3 seconds at each setting group or item the unit reverts to PV SV Display Mode ...

Page 26: ... and low limit values When changing the input from DC voltage to other inputs remove the sensor connected to this controller first then change the input If the input is changed with the sensor connected the input circuit may break With DC voltage input the side input terminal number differs as follows side input terminal number of 0 to 5V DC 1 to 5V DC 0 to 10V DC 16 side input terminal number of ...

Page 27: ...0 0 to 1 V DC 2000 to 10000 0 to 5 V DC 2000 to 10000 1 to 5 V DC 2000 to 10000 0 to 10 V DC 2000 to 10000 Scaling high limit 1370 Sets scaling high limit value Setting range Scaling low limit value to input range high limit value DC voltage current inputs 2000 to 10000 The placement of the decimal point follows the selection Scaling low limit 200 Sets scaling low limit value Setting range Input r...

Page 28: ...his corrects the input value from the sensor When a sensor cannot be set at the exact location where control is desired the sensor measured temperature may deviate from the temperature in the controlled location When controlling with multiple controllers sometimes the measured temperatures do not concur due to differences in sensor accuracy or dispersion of load capacities In such a case the contr...

Page 29: ...T2 proportional cycle Sets OUT2 proportional cycle Relay contact 30 sec Non contact voltage 3 sec For relay contact output if the proportional cycle time is decreased the frequency of the relay action increases and the life of the relay contact is shortened Available when the D option is ordered Not available if OUT2 is in ON OFF control Setting range 1 to 120 seconds OUT1 high limit 100 Sets OUT1...

Page 30: ...OUT2 low limit value Available if the D option is ordered Not available if OUT2 is in ON OFF control Setting range 0 to OUT2 high limit value Direct current output type 5 to OUT2 high limit value Overlap band Dead band 0 0 Sets the overlap band or dead band for OUT1 and OUT2 Set value Dead band Set value Overlap band Available only when the D option is ordered Setting range 200 0 to 200 0 DC volta...

Page 31: ...V when Event Input is ON Available only when EI option is ordered Setting range 0 0 to 100 0 Direct current output 5 0 to 105 0 OUT2 MV preset output 0 0 If Preset output 1 or 2 is selected in Event input allocation OUT2 MV can be set Preset output 1 Control is performed with the preset output MV if sensor is burnt out during Event Input ON Preset output 2 Control is performed with the preset outp...

Page 32: ...ts Event input EVI2 from Event input allocation table Refer to the Event input allocation table Event input EVI3 allocation 000 No event Selects Event input EVI3 from Event input allocation table Refer to the Event input allocation table Event input EVI4 allocation 000 No event Selects Event input EVI4 from Event input allocation table Refer to the Event input allocation table Event Input Allocati...

Page 33: ... The unit maintains control with the preset output MV Signal edge action from OFF to ON or from ON to OFF is engaged If 010 Program mode RUN STOP is selected in Event input EVI1 allocation the following action will be performed However only when power is turned ON level action ON Closed or OFF Open is engaged Fig 6 3 3 1 OR calculation if any one is ON closed the function activates begins if the s...

Page 34: ...oceeds to the Event output EVT1 allocation Character Setting Item Function Setting Range Factory Default Event output EVT1 allocation 000 No event Selects Event output EVT1 from the Event output allocation table Refer to the Event Output Allocation Table Event output EVT2 allocation 000 No event Selects Event output EVT2 from the Event output allocation table Refer to the Event Output Allocation T...

Page 35: ...tput Process high alarm Same as the High limit alarm 008 Alarm output Process low alarm Same as the High limit alarm 009 Alarm output High limit with standby Same as the High limit alarm 010 Alarm output Low limit with standby Same as the High limit alarm 011 Alarm output High Low limits with standby Same as the High limit alarm 012 Alarm output High Low limits with standby independent Same as the...

Page 36: ...output Program control If an alarm type is changed the alarm value will return to 0 0 0 If 001 to 012 Alarm output is selected Individual setting for event outputs If 013 to 019 is selected Common setting to the plural event outputs Available only when W or W3 option is ordered Pattern End Output After the program control is completed pattern end output is turned ON The following program pattern s...

Page 37: ... Low limits with standby independent is selected in Event output EVT2 to EVT5 allocation their setting characters will be xxx to xxx Alarm action Energized De energized When Alarm Energized is selected EVT1 output terminals 9 10 is conductive ON while the EVT1 indicator is lit EVT1 output is not conductive OFF while EVT1 indicator is not lit When Alarm De energized is selected EVT1 output terminal...

Page 38: ...g Item Function Setting Range Factory Default Timer output delay action ON delay time Selects a Timer output action ON delay time OFF delay time ON OFF delay time Delay action Fig 6 3 4 4 Timer output time unit Minutes Selects Timer output time unit Minutes Seconds OFF delay time 0 Sets OFF delay time Setting range 0 to 10000 Time unit follows the selection in Timer output time unit ON delay time ...

Page 39: ...ed alternately on the PV Display When OUT1 is ON the CT1 current value is updated When OUT1 is OFF the unit memorizes the previous value when OUT1 was ON Upon returning to set limits the alarm will stop Rated current 20 0 A 0 0 to 20 0 A 100 0 A 0 0 to 100 0 A and CT2 current alternating display on the PV Display Heater burnout alarm 2 value 0 0 A Sets the heater current value for Heater burnout a...

Page 40: ...value and if the PV does not reach the Loop break alarm band setting within the time allotted to assess the Loop break alarm the alarm output will be turned ON Likewise after MV has reached 0 or the OUT low limit value and if the PV does not drop to the Loop break alarm band setting within the time allotted to assess the Loop break alarm the alarm output will be turned ON When the control action i...

Page 41: ...time within the set step for which Time signal output is performed Time signal output ON time follows Time signal output OFF time after the program control starts The following program pattern shows that the temperature rises to 200 for 1 hour and stays at 200 for 2 hours after program control starts Step 1 2 Step SV 200 200 Step time 1 00 2 00 Time signal output Fig 6 3 4 5 is shown when set as f...

Page 42: ...ue control or Program control Fixed value control Program control Step time unit Hours Minutes Selects the step time unit for the program control Available only for the program control Hours Minutes Minutes Seconds Power restore action Selects the program status if a power Stops in standby after power is restored failure occurs mid program and it is restored Available only for the program control ...

Page 43: ...nge Factory Default Communication protocol Shinko protocol Selects communication protocol Shinko protocol MODBUS ASCII mode MODBUS RTU mode Instrument number 0 Sets the instrument number The instrument numbers should be set one by one when multiple instruments are connected in Serial communication otherwise communication is impossible Setting range 0 to 95 Communication speed 9600 bps Selects a co...

Page 44: ...s value to the value received via SV digital transmission SVTC command Available only when Shinko protocol is selected in Communication protocol Setting range Converted value of 20 of input span DC voltage current inputs 20 of scaling span The placement of the decimal point follows the selection ...

Page 45: ...et in analog by the remote operation externally External setting input high limit 1370 Sets External setting input high limit value For EA1 4 20 mA option the value corresponds to 20 mA input Setting range External setting input low limit to Input range high limit The placement of the decimal point follows the selection External setting input low limit 200 Sets External setting input low limit val...

Page 46: ...transmission SV transmission MV transmission DV transmission Transmission output high limit 1370 Sets the Transmission output high limit value For TA1 4 20 mA option the value correponds to 20 mA output Setting range PV SV transmission Transmission output low limit to Input range high limit value MV transmission Transmission output low limit value to 105 0 DV transmission Transmission output low l...

Page 47: ...can be changed Lock 3 None of the set values can be changed as Lock 1 Lock 4 SV and Alarm value can be changed Other set values cannot be changed PID zone function Not used Selects Not used Used of the PID zone function Control is performed by automatic change of PID zone parameters which are linked to the SV or step SV for program control PID zone value can be set in the PID group Refer to PID zo...

Page 48: ...it Selects the display to backlight All Displays and indicators are backlit PV Display is backlit SV MV TIME MV DV Bar Graph Displays are backlit Action indicators are backlit PV SV MV TIME MV DV Bar Graph Displays are backlit PV Display Action indicators are backlit SV MV TIME MV DV Bar Graph Displays Action indicators are backlit PV color Red Selects PV Display color See PV Display color selecti...

Page 49: ...ne value is lower than the current one the next PID zone parameters will not be effective During program control the currently performing step SV is applicable to the PID zone In the case of Fig 6 3 9 1 SV 150 is higher than PID zone value 1 100 and lower than PID zone value 2 200 so control is performed using PID zone parameters of PID zone value 2 As PID zone value 4 has not been set even in the...

Page 50: ...g PV is lower than SV PV color range Orange PV is within SV PV color range Green PV is higher than SV PV color range Red Hys Set point of PV color range Fig 6 3 9 2 PV color changes continuously Orange Green Red Any alarm output from EVT1 to EVT5 is ON Red PV color changes depending on the PV color range setting When any alarm output from EVT1 to EVT5 is ON the PV Display turns red PV is lower tha...

Page 51: ...ght in accordance with the OUT1 MV MV indication when Heating Cooling control output is ordered Scale shows that center is 0 the right end OUT1 MV is 105 and the left end OUT2 MV is 105 Segments for OUT1 MV light increasingly to the right from the center Segments for OUT2 MV light increasingly to the left from the center DV indication In the case of deviation zero 0 central 2 segments light For po...

Page 52: ...ed by terminal connection can be set To set other Set value memory number select it again by connecting terminals Character Setting Item Function Setting Range Factory Default EVT1 alarm value 0 Sets EVT1 alarm value If the independent alarm High Low limits independent High Low limit range independent or High Low limits with standby independent is selected in Event output EVT1 allocation the EVT1 ...

Page 53: ... or High Low limits with standby independent is selected in Event output EVT2 allocation Setting range Refer to Table 7 1 2 1 on p 55 EVT3 alarm value 0 Sets EVT3 alarm value If the independent alarm High Low limits independent High Low limit range independent or High Low limits with standby independent is selected in Event output EVT3 allocation the EVT3 alarm value matches the EVT3 low limit ala...

Page 54: ... or High Low limits with standby independent is selected in Event output EVT4 allocation Setting range Refer to Table 7 1 2 1 on p 55 EVT5 alarm value 0 Sets EVT5 alarm value If the independent alarm High Low limits independent High Low limit range independent or High Low limits with standby independent is selected in Event output EVT5 allocation the EVT5 alarm value matches the EVT5 low limit ala...

Page 55: ...s high alarm Input range low limit to input range high limit value 2 Process low alarm Input range low limit to input range high limit value 2 High limit with standby alarm deviation setting Input span to input span 1 Low limit with standby alarm deviation setting Input span to input span 1 High Low limits with standby alarm deviation setting 0 to input span 1 High Low limits with standby independ...

Page 56: ...e D option is ordered Not available if OUT1 is in ON OFF control Setting range 0 0 to 10 0 times Multiplied value of OUT1 proportional band Integral time 200 seconds Sets integral time for OUT1 Setting the value to 0 disables this function Not available if OUT1 is in ON OFF control Auto reset can be performed when PD is control action I 0 Setting range 0 to 3600 seconds Derivative time 50 seconds ...

Page 57: ...g control if PV is lower than SV output is generally turned from OFF to ON as shown in Fig 7 1 3 1 If OUT1 rate of change is set the output can be changed by the rate of change Fig 7 1 3 2 This control is suitable for high temperature heaters which are made from molybdenum tungsten or platinum etc and used at approx 1500 to 1800 which are easily burnt out from turning on electricity rapidly Usual ...

Page 58: ...s selected in Event input allocation setting items in this group can be set for the selected memory numbers To enter the SV Event group follow the procedure below 1 Press the key in PV SV Display Mode The unit proceeds to the SV Event group 2 Press the key The unit proceeds to the SV1 Character Setting Item Function Setting Range Factory Default SV1 0 Sets SV1 Setting range Scaling low limit to Sc...

Page 59: ...lue Setting the value to 0 or 0 0 disables this alarm except Process high and Process low alarm Available when the independent alarm High Low limits independent High Low limit range independent or High Low limits with standby independent is selected in Event output EVT2 allocation Setting range Refer to Table 7 1 2 1 on p 55 EVT3 alarm value 0 Sets EVT3 alarm value If the independent alarm High Lo...

Page 60: ...nt is selected in Event output EVT4 allocation Setting range Refer to Table 7 1 2 1 on p 55 EVT5 alarm value 0 Sets EVT5 alarm value If the independent alarm High Low limits independent High Low limit range independent or High Low limits with standby independent is selected in Event output EVT5 allocation the EVT5 alarm value matches the EVT5 low limit alarm value Setting the value to 0 or 0 0 dis...

Page 61: ... 0 disables this alarm except Process high and Process low alarm Available when the independent alarm High Low limits independent High Low limit range independent or High Low limits with standby independent is selected in Event output EVT5 allocation Setting range Refer to Table 7 1 2 1 on p 55 ...

Page 62: ...When program pattern is rising PV is higher than SV Wait value When program pattern is falling PV is lower than SV Wait value Step 1 2 3 4 5 PV Program pattern Program pattern delayed by T due to the Wait function Fig 7 2 2 2 200 0 T T If PV becomes higher than 190 the wait function will be released and proceeds to Step 2 Wait value 10 As PV is not in the range of SV Wait value the unit is in Wait...

Page 63: ...ep1 EVT1 alarm value If the independent alarm High Low limits independent High Low limit range independent or High Low limits with standby independent is selected in Event output EVT1 allocation the EVT1 alarm value matches the EVT1 low limit alarm value Setting the value to 0 or 0 0 disables this alarm except Process high and Process low alarm Not available if No event is selected in Event output...

Page 64: ... limits with standby independent is selected in Event output EVT3 allocation the EVT3 alarm value matches the EVT3 low limit alarm value Setting the value to 0 or 0 0 disables this alarm except Process high and Process low alarm Not available if No event is selected in Event output EVT3 allocation Available when the Alarm output is selected in Event output EVT3 allocation Setting range Refer to Ta...

Page 65: ...nt output EVT5 allocation Setting range Refer to Table 7 1 2 1 on p 55 Step 1 EVT5 high limit alarm value 0 Sets Step 1 EVT5 high limit alarm value Setting the value to 0 or 0 0 disables this alarm except Process high and Process low alarm Available when the independent alarm High Low limits independent High Low limit range independent or High Low limits with standby independent is selected in Eve...

Page 66: ... available if PID zone function Not used is selected in PID zone function One zone contains from PID zone value 1 to OUT1 rate of change 1 When SV is lower than Reference value 1 PID zone value 1 control is performed with these PID zone parameters Setting range Scaling low limit value to Scaling high limit value OUT1 proportional band 1 10 Sets proportional band 1 for OUT1 OUT1 becomes ON OFF cont...

Page 67: ...ID zone function one zone contains data from PID zone value 1 to OUT1 rate of change 1 Up to 5 zones can be set repeatedly OUT1 rate of change 5 0 second Sets OUT1 rate of change 5 changing value of OUT1 MV for 1 second Setting the value to 0 disables this function See OUT1 rate of change below Setting range 0 to 100 second OUT1 rate of change For Heating control if PV is lower than SV output is g...

Page 68: ...ntrol or Auto reset Perform Cancel in P control or PD control If PID zone function Used is selected values such as P I D ARW of the PID block number which are used for control will be changed after AT is finished If AT is cancelled during the process P I D and ARW values return to the values before AT was performed AT will be forced to stop if it has not been completed within 4 hours Auto reset is...

Page 69: ...conds See Table 8 1 1 Table 8 1 1 Sensor Input PV Display SV MV TIME Display PV Display SV MV TIME Display K J R S B E T N PL C W Re5 26 Pt100 JPt100 Pt100 JPt100 Pt100 Pt100 4 to 20 mA DC 0 to 20 mA DC 0 to 10 mV DC 10 to 10 mV DC 0 to 50 mV DC 0 to 100 mV DC 0 to 1 V DC 0 to 5 V DC 1 to 5 V DC 0 to 10 V DC Scaling high limit value During this time all outputs and indicators are in OFF status Con...

Page 70: ...control Program control Fixed value control Control action starts so as to keep the control target at the SV Program control Perform program control To perform Program control press the key Program control starts PV start is used PV start When the program control starts the step SV and time are advanced to the PV and the control starts If Program start temperature has been set in the Program group...

Page 71: ...t turning OFF their power supplies using this function This function is available for Fixed value control To turn the control output OFF press the key for approximately 1 second in PV SV Display Mode is indicated on the PV Display while the function is working However indication on the PV Display depends on the selection in Indication when output OFF Once the control output OFF function is enabled...

Page 72: ...E Display indicates the output MV and the MEMO STEP Display indicates SV and TIME of the SV MV TIME indicator are unlit and MV of the SV MV TIME indicator lights If the key is pressed again during Fixed value control the unit will revert to PV SV Display Mode If the key is pressed during program control remaining step time is indicated on the SV MV TIME Display SV and MV of the SV MV TIME indicato...

Page 73: ...it proceeds to the AT group 2 Press the key The unit proceeds to AT Auto reset 3 Select AT Auto reset Cancel with the key and press the key for 3 seconds AT will stop and the unit will revert to PV SV Display Mode If AT is cancelled during this process each value of P I D and ARW reverts to the values before the AT was performed AT Perform Cancel PID control 1 Proceed to the AT group Press the key...

Page 74: ...ceed to the Input group Press the key The unit proceeds to the Input group 3 Proceed to the Event output group Press the key multiple times until Event output group characters appear 4 Proceed to Event output EVT1 allocation Press the key The unit proceeds to Event output EVT1 allocation 5 Select Event output EVT1 allocation Select 004 Alarm output High Low limits independent with the or key 6 Con...

Page 75: ...etting mode Press the and keys in that order together in PV SV Display Mode The unit proceeds to Event setting mode 2 Set the EVT1 low limit alarm value Set the EVT1 low limit alarm value with the or key 3 Register the EVT1 low limit alarm value Press the key The EVT1 low limit alarm value is registered and the unit proceeds to EVT1 high limit alarm value 4 Set EVT1 high limit alarm value Set the ...

Page 76: ...No Connecting terminals 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 11 15 DI1 EVI1 COM X X X X X X X X 12 15 DI2 EVI2 COM X X X X X X X X 13 15 DI3 EVI3 COM X X X X X X X X 14 15 DI4 EVI4 COM X X X X X X X X Works as Set value memory number 15 If Set value memory is selected for EVI1 and EVI2 in Event input EVI1 to EVI4 allocation Set value memory number can be selected using terminals 11 12 and 15 as sho...

Page 77: ...alue EVT3 high limit alarm value EVT4 alarm value EVT4 high limit alarm value EVT5 alarm value EVT5 high limit alarm value Registration complete Data is registered in the file number indicated by the MEMO STEP Display When any number is retrieved by connecting terminals the selected number will be indicated and the control is performed using the data set values of the indicated file number To chan...

Page 78: ...l band during the PD control Since the corrected value is internally memorized it is not necessary to perform the auto reset again as long as the process is the same However when OUT1 proportional band P is set to 0 or 0 0 the corrected value is cleared Fig 9 1 Auto reset is performed Offset is corrected Offset span Temperature Time SV ...

Page 79: ...ed during this process each value of P I D and ARW reverts to the values before the AT was performed AT will be forced to stop if it has not been completed within 4 hours If Direct Reverse action is switched during AT by selecting 003 Direct Reverse action in Event input allocation the AT stops During AT none of the setting items can be set If power failure occurs during AT the AT will stop Someti...

Page 80: ... constants 2 PID constants calculated 3 Controlled by the PID constant set by AT Fig 10 3 3 If there is a large difference between the SV and PV as the temperature is falling When AT bias is set to 20 the AT process will fluctuate at the temperature 20 higher than the SV 1 Calculates PID constants 2 PID constants calculated 3 Controlled by the PID constants set by AT 4 AT bias value Fig 10 4 1 2 3...

Page 81: ...se action Cooling direct action Proportional band Proportional band Changes continuously according to deviation Cycle action is performed according to deviation Cycle action is performed according to deviation Cycle action is performed according to deviation Unlit Lit Unlit Lit Indicator OUT1 S A 12 0 V DC 0 V DC 0 V DC 12 V DC 0 12 V DC 12 V DC 20 mA DC 20 to 4 mA DC 4 mA DC 4 mA DC 4 to 20 mA DC...

Page 82: ...6 4 mA DC 5 6 4 mA DC 5 6 20 mA DC 4 5 6 H C L 4 5 6 H C L 4 5 6 H C L 4 5 6 H C L OFF ON SV OFF ON SV Cooling direct action Heating reverse action Lit Unlit Hysteresis Hysteresis Control action Indicator Lit Unlit OUT1 11 2 OUT1 ON OFF Control Action ON lit or OFF unlit ...

Page 83: ...larm EVT1 hysteresis EVT1 hysteresis Alarm action Alarm output Alarm action Alarm output Alarm action Alarm output Alarm action Alarm output EVT1 value EVT1 value EVT1 value EVT1 value EVT1 hysteresis EVT1 hysteresis EVT1 hysteresis EVT1 hysteresis EVT1 hysteresis EVT1 value EVT1 value SV side side side side EVT1 value EVT1 value SV EVT1 value EVT1 low limit value EVT1 high limit value EVT1 low li...

Page 84: ...nals 7 and 10 EVT4 output terminals 29 and 30 EVT5 output terminals 28 and 30 For the alarm types High limit alarm High Low limits alarm High Low limits independent Process high alarm the alarm is activated when the indication is overscale and the standby function is released for the alarms with standby function For the alarm types Low limit alarm High Low limits alarm High Low limits independent ...

Page 85: ...and 10 are closed ON and turns off when their output terminals 9 and 10 are opened OFF The following shows EVT2 to EVT5 terminals EVT2 output terminals 7 and 8 For A3 option use terminals 8 and 10 EVT3 output terminals 7 and 10 EVT4 output terminals 29 and 30 EVT5 output terminals 28 and 30 ...

Page 86: ...ting action Control action Cooling action Cycle action is performed according to deviation Cycle action is performed according to deviation Cycle action is performed according to deviation Cycle action is performed according to deviation Changes continuously according to deviation Unlit Lit Indicator Indicator Unlit Lit Heating P band Cooling P band OUT1 OUT2 11 5 OUT2 Heating Cooling control Acti...

Page 87: ... action is performed according to deviation Changes continuously according to deviation Changes continuously according to deviation Lit Unlit Unlit Lit Cycle action is performed according to deviation Cycle action is performed according to deviation Heating action Cooling action Cooling P band Heating P band Dead band Control action Indicator Indicator 11 6 OUT2 Heating Cooling Control Action When...

Page 88: ...cording to deviation Cycle action is performed according to deviation Cycle action is performed according to deviation Changes continuously according to deviation Changes continuously according to deviation Unlit Lit Unlit Lit Indicator Indicator 4 to 20mA DC 20 to 4mA DC Cooling action Heating action Heating action Overlap band Control action Cooling P band 11 7 OUT2 Heating Cooling Control Actio...

Page 89: ...ax 10 to 10 mV DC 40 max 0 to 50 mV DC 200 max 0 to 100 mV DC 200 max 0 to 1 V DC 2 k max 0 to 5 V DC 1 to 5 V DC 0 to 10 V DC Input impedance 100 k minimum Allowable input voltage 15 V DC max Allowable signal source resistance 100 max Power supply voltage 100 to 240 V AC 50 60 Hz or 24 V AC DC 50 60 Hz Allowable voltage fluctuation 100 to 240 V AC 85 to 264 V AC 24 V AC DC 20 to 28 V AC DC Genera...

Page 90: ...ithin 0 4 of input span 1 digit RTD Within 0 1 of each input span 1 digit Direct current Within 0 2 of each input span 1 digit DC voltage Within 0 2 of each input span 1 digit External setting input accuracy Within 0 2 of External setting input span Cold junction temperature compensation accuracy Within 1 at 0 to 50 Input sampling period 125 ms 250 ms when EA or EV option is ordered Time accuracy ...

Page 91: ...to 100 Direct current 5 to 105 Factory default 0 Control output OUT1 Relay contact 1a1b Control capacity 3 A 250 V AC resistive load 1 A 250 V AC inductive load cos 0 4 Electrical life 100 000 cycles Non contact voltage SSR drive 12 V DC 15 Maximum 40 mA short circuit protected Direct current 4 to 20 mA DC Resolution 12000 Load resistance Maximum 600 Standard functions EVT1 output The output is tu...

Page 92: ...o 10000 The placement of the decimal point follows the selection Output EVT output for which Alarm output is selected in Event output allocation Loop break alarm Detects heater burnout sensor burnout and actuator trouble Setting range Loop break alarm time 0 to 200 minutes Loop break alarm band 0 to 150 0 0 to 150 0 DC voltage current inputs 0 to 1500 The place ment of the decimal point follows th...

Page 93: ...the PV Display flashes For 0 to 20 mA DC 0 to 5 V DC and 0 to 10 V DC inputs the PV display indicates the value corresponding with 0 mA or 0 V input Input error indication Contents Indication Output status OUT1 OUT2 Direct Cooling Reverse Heating Direct Cooling Reverse Heating Overscale Measured value has exceeded Indication range high limit value flashes OFF 4 mA or OUT1 low limit value OFF 4 mA ...

Page 94: ...allocation this function activates If Event input turns ON timer counting starts and Event output turns ON or OFF after delay time has passed If the timer function is allocated to the Event input which is linked to control control turns ON while Event output is ON and turns OFF if Event output is OFF Bar graph The bar graph lights depending on the selection of either MV or DV With MV indication if...

Page 95: ...is ordered Accessories sold separately Terminal cover Heater burnout alarm 20 A CT CTL 6 S H Heater burnout alarm 100 A CT CTL 12 S36 10L1U USB communication cable CMB 001 12 2 Optional Specifications Event input Option code EI EVI1 to EVI4 are used as an Event input Any Events selected in Event input allocation will be performed depending on the Input ON Closed or OFF Open status See Fig 6 3 3 1 ...

Page 96: ...rrent 100 A Off when set to 0 0 Setting accuracy Within 5 of the rated current Action point Heater burnout alarm value Action ON OFF action Output Relay contact 1a Control capacity 3 A 250 V AC resistive load 1 A 250 V AC inductive load cos 0 4 Electric life 100 000 cycles Heating Cooling control Option code D OUT2 propor tional band 0 0 to 10 0 times Multiplied value of OUT1 proportional band ON ...

Page 97: ...us set values 2 Reading of the PV and action status 3 Function change Cable length Max 15 m C Max 1 2 km C5 Cable resistance Within 50 Terminators are not necessary but if used use a terminator of 120 minimum on both sides Communication line EIA RS 232C C EIA RS 485 C5 Communication method Half duplex communication Synchronization method Start stop synchronization Communication speed 9600 19200 38...

Page 98: ... 0 to 1 V DC Option code EV1 1 to 5 V DC Option code EV2 Allowable input EA 50 mA DC max EV1 5 V DC max EV2 10 V DC max Input impedance EA 50 EV 100 k Input sampling period 250 ms Transmission output Option code TA1 TV1 Converting the value PV SV MV or DV transmission to analog signal every 125 ms outputs the value in current or voltage Factory default PV transmission If Transmission output high l...

Page 99: ...V DC 0 to 1 V DC If the input terminals of the instrument are shorted and if a scaling low limit value is indicated the instrument is likely to be operating normally however the signal wire may be disconnected Check whether the input terminals of thermocouple RTD or DC voltage 0 to 10 mV DC 10 to 10 mV DC 0 to 50 mV DC 0 to 100 mV DC 0 to 1 V DC are securely mounted to the instrument input termina...

Page 100: ...nnected Check whether the input lead wire terminals for DC voltage 0 to 5 V DC 0 to 10 V DC or direct current 0 to 20 mA DC are securely mounted to the instrument input terminals The indication of PV display is irregular or unstable Check whether sensor input or temperature unit is correct Select the sensor input and temperature unit properly Sensor correcting value is unsuitable Set it to a suita...

Page 101: ...rol output terminals are mounted to the instrument input terminals securely Check whether the wiring of sensor or control output terminals is correct The control output remains in an ON status OUT1 or OUT2 low limit value is set to 100 or higher Set it to a suitable value The control output remains in an OFF status OUT1 or OUT2 high limit value is set to 0 or less Set it to a suitable value For al...

Page 102: ...h limit alarm value Setting range Refer to Table 14 1 on p 103 EVT2 alarm value Setting range Refer to Table 14 1 on p 103 EVT2 high limit alarm value Setting range Refer to Table 14 1 on p 103 EVT3 alarm value Setting range Refer to Table 14 1 on p 103 EVT3 high limit alarm value Setting range Refer to Table 14 1 on p 103 EVT4 alarm value Setting range Refer to Table 14 1 on p 103 EVT4 high limit...

Page 103: ...n to Input span 1 High Low limits with standby Deviation setting 0 to Input span 1 High Low limits with standby independent Deviation setting 0 to Input span 1 1 For DC voltage current inputs the input span is the same as the scaling span 2 For DC voltage current inputs input range low or high limit value is the same as scaling low or high limit value PID setting mode Character Setting Item Settin...

Page 104: ...rm value Setting range Refer to Table 14 1 on p 103 EVT2 high limit alarm value Setting range Refer to Table 14 1 on p 103 EVT3 alarm value Setting range Refer to Table 14 1 on p 103 EVT3 high limit alarm value Setting range Refer to Table 14 1 on p 103 EVT4 alarm value Setting range Refer to Table 14 1 on p 103 EVT4 high limit alarm value Setting range Refer to Table 14 1 on p 103 EVT5 alarm valu...

Page 105: ... high limit alarm value Setting range Refer to Table 14 1 on p 103 Step 1 EVT2 alarm value Setting range Refer to Table 14 1 on p 103 Step 1 EVT2 high limit alarm value Setting range Refer to Table 14 1 on p 103 Step 1 EVT3 alarm value Setting range Refer to Table 14 1 on p 103 Step 1 EVT3 high limit alarm value Setting range Refer to Table 14 1 on p 103 Step 1 EVT4 alarm value Setting range Refer...

Page 106: ...t alarm value Step 3 SV Step 3 time Step 3 Wait value Step 3 EVT1 alarm value Step 3 EVT1 high limit alarm value Step 3 EVT2 alarm value Step 3 EVT2 high limit alarm value Step 3 EVT3 alarm value Step 3 EVT3 high limit alarm value Step 3 EVT4 alarm value Step 3 EVT4 high limit alarm value Step 3 EVT5 alarm value Step 3 EVT5 high limit alarm value Step 4 SV Step 4 time Step 4 Wait value Step 4 EVT1...

Page 107: ...ait value Step 6 EVT1 alarm value Step 6 EVT1 high limit alarm value Step 6 EVT2 alarm value Step 6 EVT2 high limit alarm value Step 6 EVT3 alarm value Step 6 EVT3 high limit alarm value Step 6 EVT4 alarm value Step 6 EVT4 high limit alarm value Step 6 EVT5 alarm value Step 6 EVT5 high limit alarm value Step 7 SV Step 7 time Step 7 Wait value Step 7 EVT1 alarm value Step 7 EVT1 high limit alarm va...

Page 108: ...high limit alarm value Step 9 EVT2 alarm value Step 9 EVT2 high limit alarm value Step 9 EVT3 alarm value Step 9 EVT3 high limit alarm value Step 9 EVT4 alarm value Step 9 EVT4 high limit alarm value Step 9 EVT5 alarm value Step 9 EVT5 high limit alarm value Step 10 SV Step 10 time Step 10 Wait value Step 10 EVT1 alarm value Step 10 EVT1 high limit alarm value Step 10 EVT2 alarm value Step 10 EVT2...

Page 109: ...rm value Step 12 EVT2 high limit value Step 12 EVT3 alarm value Step 12 EVT3 high limit alarm value Step 12 EVT4 alarm value Step 12 EVT4 high limit alarm value Step 12 EVT5 alarm value Step 12 EVT5 high limit alarm value Step 13 SV Step 13 time Step 13 Wait value Step 13 EVT1 alarm value Step 13 EVT1 high limit alarm value Step 13 EVT2 alarm value Step 13 EVT2 high limit alarm value Step 13 EVT3 ...

Page 110: ...alarm value Step 14 EVT5 alarm value Step 14 EVT5 high limit alarm value Step 15 SV Step 15 time Step 15 Wait value Step 15 EVT1 alarm value Step 15 EVT1 high limit alarm value Step 15 EVT2 alarm value Step 15 EVT2 high limit alarm value Step 15 EVT3 alarm value Step 15 EVT3 high limit alarm value Step 15 EVT4 alarm value Step 15 EVT4 high limit alarm value Step 15 EVT5 alarm value Step 15 EVT5 hi...

Page 111: ...portional band Integral time 1 Setting range 0 to 3600 seconds Derivative time 1 Setting range 0 to 1800 seconds ARW 1 Setting range 0 to 100 Manual reset 1 Setting range 1000 0 DC voltage current inputs The placement of the decimal point follows the selection OUT1 rate of change 1 Setting range 0 to 100 sec PID zone value 2 OUT1 proportional band 2 OUT2 proportional band 2 Integral time 2 Derivat...

Page 112: ...W 4 Manual reset 4 OUT1 rate of change 4 PID zone value 5 OUT1 proportional band 5 OUT2 proportional band 5 Integral time 5 Derivative time 5 ARW 5 Manual reset 5 OUT1 rate of change 5 AT group Character Setting Item Setting Range Data AT group AT Auto reset AT Auto reset Cancel AT Auto reset Perform AT bias Setting range 0 to 50 0 to 100 With a decimal point 0 0 to 50 0 0 0 to 100 0 ...

Page 113: ... J 200 to 1000 R 0 to 1760 S 0 to 1760 B 0 to 1820 E 200 to 800 T 200 0 to 400 0 N 200 to 1300 PL 0 to 1390 C W Re5 26 0 to 2315 Pt100 200 0 to 850 0 JPt100 200 0 to 500 0 Pt100 200 to 850 JPt100 200 to 500 Pt100 100 0 to 100 0 Pt100 100 0 to 500 0 K 328 to 2498 K 328 0 to 752 0 J 328 to 1832 R 32 to 3200 S 32 to 3200 B 32 to 3308 E 328 to 1472 T 328 0 to 752 0 N 328 to 2372 PL 32 to 2534 ...

Page 114: ...to Input range high limit DC voltage current inputs 2000 to 10000 The placement of the decimal point follows the selection Scaling low limit Setting range Input range low limit to Scaling high limit DC voltage current inputs 2000 to 10000 The placement of the decimal point follows the selection Decimal point place No decimal point 1 digit after decimal point 2 digits after decimal point 3 digits a...

Page 115: ...ction OUT2 cooling method Air cooling linear characteristics Oil cooling 1 5th power of the linear characteristics Water cooling 2nd power of the linear characteristics OUT2 high limit Setting range OUT2 low limit to 100 Direct current output OUT2 low limit to 105 OUT2 low limit Setting range 0 to OUT2 high limit Direct current output 5 to OUT2 high limit Overlap Dead band Setting range 200 0 to 2...

Page 116: ...I4 allocation Refer to Event Input Allocation Table Event Input Allocation Table Selected value Event input function Input ON Closed Input OFF Open Remarks 000 No event 001 Set value memory 2n 1 n 0 to 3 002 Control ON OFF Control OFF Control ON Control output OFF function 003 Direct Reverse action Direct action Reverse action Always effective 004 Timer Start Stop Start Stop 005 PV Display PV hold...

Page 117: ...s turned on 013 Integral action holding Integral action Holding Standard integral action Control continues with the integral value being held 014 Preset output 2 Preset output Standard control The unit maintains control with the preset output MV Event output group Character Setting Item Setting Range Data Event output group Event output EVT1 allocation Refer to Event Output Allocation Table Event ...

Page 118: ... output Process high alarm Same as the High limit alarm 008 Alarm output Process low alarm Same as the High limit alarm 009 Alarm output High limit with standby Same as the High limit alarm 010 Alarm output Low limit with standby Same as the High limit alarm 011 Alarm output High Low limits with standby Same as the High limit alarm 012 Alarm output High Low limits with standby independent Same as ...

Page 119: ...etting Item Setting Range Data Alarm hysteresis Setting range 0 1 to 1000 0 DC voltage current inputs 1 to 10000 The placement of the decimal point follows the selection Alarm delay time 0 to 10000 seconds Alarm Energized De energized Energized De energized If any alarm output from 001 Alarm output High limit alarm to 012 Alarm output High Low limits with standby independent is selected in Event o...

Page 120: ...ation Character Setting Item Setting Range Data Loop break alarm time 0 to 200 minutes Loop break alarm band 0 to 150 or 0 0 to 150 0 DC voltage current inputs 0 to 1500 The placement of the decimal point follows the selection Time signal output setting items When Time signal output is selected in Event output allocation Character Setting Item Setting Range Data Time signal output step Setting ran...

Page 121: ...wer is restored Suspends on hold after power is restored Program start temperature Setting range Scaling low limit to Scaling high limit value Communication group Character Setting Item Setting Range Data Communication group Communication protocol Shinko protocol MODBUS ASCII mode MODBUS RTU mode Instrument number Setting range 0 to 95 Communication speed 9600 bps 19200 bps 38400 bps Data bit Pari...

Page 122: ...tting input high limit Setting range External setting input low limit to Input range high limit External setting input low limit Setting range Input range low limit to External setting input high limit Remote bias Setting range Converted value of 20 of input span DC voltage current inputs 20 of scaling span The placement of the decimal point follows the selection Transmission Output Group Characte...

Page 123: ...ange Data Other function group Set value lock Unlock All set values can be changed Lock 1 None of the set values can be changed Lock 2 Only SV can be changed Lock 3 None of the set values can be changed as Lock 1 Lock 4 SV and Alarm value can be changed Other set values cannot be changed PID zone function Not used Used SV rise rate Setting range 0 to 10000 minute minute Thermocouple RTD inputs wit...

Page 124: ...ators are backlit PV color Green Red Orange When any alarm output from EVT1 to EVT5 is ON PV color turns from green to red When any alarm output from EVT1 to EVT5 is ON PV color turns from orange to red PV color changes continuously Orange Green Red PV color changes continuously Orange Green Red and simultaneously when any alarm output from EVT1 to EVT5 is ON Red PV color range Setting range 0 1 t...

Page 125: ...m value EVT2 high limit alarm value EVT3 alarm value EVT3 high limit alarm value EVT4 alarm value EVT4 high limit alarm value EVT5 alarm value EVT5 high limit alarm value Time signal output ON OFF PID zone value 1 2 3 4 5 OUT1 proportional band OUT2 proportional band Integral time Derivative time ARW Manual reset OUT1 rate of change ...

Page 126: ...126 7 8 9 10 11 12 13 14 15 ...

Page 127: ...de illustrated by an arrow MODE Press the and MODE keys in that order together MODE 3 sec Press and hold the and MODE keys in that order together for 3 seconds MODE 3 sec Press and hold the MODE key for 3 seconds Setting item The PV Display indicates setting characters and the SV MV TIME Display indicates the factory default Setting items with dotted lines are optional and they appear only when th...

Page 128: ...ove settings up to Block 5 AT Auto reset A M B MODE MODE A M B MODE AT bias MODE MODE A M B MODE Input group MODE Input type A M B MODE MODE A M B MODE Scaling high limit MODE MODE A M B MODE MODE Scaling low limit A M B MODE MODE Decimal point place A M B MODE MODE PV filter time constant A M B MODE MODE Sensor correction Output group OUT1 proportional cycle A M B MODE MODE A M B MODE OUT2 propor...

Page 129: ...ing input low limit A M B MODE MODE Remote bias A M B MODE SET Transmission output group Transmission output type A M B MODE MODE A M B MODE Transmission output high limit MODE MODE A M B MODE MODE Transmission output low limit A M B MODE SET Other function group Set value lock A M B MODE MODE A M B MODE PID zone function MODE MODE A M B MODE MODE SV rise rate A M B MODE MODE SV fall rate A M B MO...

Page 130: ... MODE MODE A M B MODE MODE OUT1 high limit A M B MODE MODE OUT1 low limit A M B MODE MODE OUT1 ON OFF hysteresis A M B MODE MODE OUT2 cooling method A M B MODE MODE OUT2 high limit A M B MODE MODE OUT2 low limit A M B MODE MODE Overlap Dead band A M B MODE MODE OUT2 ON OFF hysteresis A M B MODE MODE Direct Reverse action A M B MODE MODE OUT1 MV preset value A M B MODE MODE OUT2 MV preset value SET...

Page 131: ...A M B MODE MODE Backlight time A M B MODE MODE Bar graph A M B MODE MODE Deviation unit SET A M B MODE MODE Stop bit A M B MODE MODE SVTC bias Alarm hysteresis MODE MODE Alarm delay time MODE Alarm Energized De energized If Alarm output is selected in Event output EVTx allocation Timer output delay action MODE MODE Timer output time unit MODE OFF delay time MODE ON delay time If Timer output is se...

Page 132: ...on A3 C5 Serial number No 123456789 In addition to the above please let us know the details of the malfunction or discrepancy and the operating conditions No ACDR11E10 2020 03 SHINKO TECHNOS CO LTD OVERSEAS DIVISION Head Office URL E mail 2 5 1 Senbahigashi Minoo Osaka Japan http www shinko technos co jp e overseas shinko technos co jp Tel Fax 81 72 727 6100 81 72 727 7006 ...

Reviews: