25
(Ex.) If used voltage is 208 V and voltage drops by 10.4 V.
Three-phase: Cabtyre cables
(Unit: AWG)
Length 100 ft (30 m)
or less
200 ft
(61 m)
300 ft
(91 m)
400 ft
(122 m)
500 ft
(152 m)
600 ft
(183 m)
Current
50 A
10
6
6
4
2
2
100 A
6
4
2
1
1/0
1/0
150 A
6
2
1
1/0
2/0
3/0
200 A
4
1
1/0
3/0
4/0
4/0
250 A
2
1/0
2/0
4/0
-
-
300 A
2
1/0
3/0
4/0
-
-
(Ex.) If used voltage is 120 V and voltage drops by 6 V.
Single-phase Cabtyre cables
(Unit: AWG)
Length
100 ft. (30 m)
or less
200 ft. (61 m)
300 ft. (91 m)
400 ft. (122 m)
Current
10 A
14
10
8
8
20 A
10
8
6
4
30 A
8
6
4
2
50 A
6
4
2
1
100 A
4
1
2/0
3/0
150 A
2
2/0
4/0
-
200 A
1
3/0
-
-
250 A
1/0
4/0
-
-
300 A
2/0
-
-
-
350 A
2/0
-
-
-
400 A
3/0
-
-
-
450 A
3/0
-
-
-
500 A
4/0
-
-
-