22
5-7. Fuel Piping Switch (3Way Fuel Valve)
Change the three-way fuel valve to switch to supply fuel from the external tank. In that case,
the internal fuel tank will not be used.
(1) If using the internal fuel tank
Change the lever of the three-
way fuel valve turned to the “B” side to supply fuel from the
internal tank. It is turned to the
“B” side when the generator is shipped from the factory.
< Note >
When disconnecting piping from the external tank, turn the lever to the “B” side, and attach
the bundled plug (R1/2
”) to the external tank fuel inlet / return.
(2) If using an external fuel tank
Connect hoses from the external fuel tank to the external fuel inlet and the external fuel return.
Change the lever of the 3way fuel valve to the “A” side to supply fuel from the external tank.
Refer to “
9-6. Connecting with External Fuel Tank
” for corresponding procedures.
5-8. Load Bank Control Switch
This equipment is adopted Load Bank Control Switch to
improve carbon debris in a muffler or extreme light load
rated load.
To activate this function, turn ON the Load Bank Control
Switch on the control panel.
< Note >
Select Load Bank Switch to ON position when remaining three phase output indicator is
displaying more than 126kVA.
CAUTION : FIRE
Always make sure that the engine is stopped when working on piping.
Always be sure to wipe up any spilled fuel.
After working on the piping, check that there is no fuel leakage.
Position B
Position A
3Way Fuel Valve
External Fuel Inlet
External Fuel Return