Detailed Function Description
55
adjustment is stronger. This function code is 1.00s means when the
change rate of deviation of PID setting and feedback is
10.00Vwithin 1s, the output frequency command of PID regulator
is 10.00Hz (ignore the role of proportion and integral).
Notice: when the function code is 0, means that the differential
regulation is prohibited.
5.1.10 Traverse frequency setting
P0-051
Traverse
Setting range:0.0~100.0%
(relative to setting frequency)
Factory value
:
0.0%
amplitude
P0-052
Jitter frequency
Setting range:0.0~50.0
%
(relative
to
traverse
amplitude
)
Factory value
:
0.0
%
P0-053
Rise
time
of
traverse
Setting range
:
0.1
~
3200.0s
Factory value
:
15.0s
P0-054
Fall
time
of
traverse
Setting range
:
0.1
~
3200.0s
Factory value
:
15.0s
Traverse frequency function applies to textile and chemical fiber
industries.When traverse frequency running, the output frequency
of inverter will traverse up and down according to setting frequency
as the center.
when the traverse amplitude is set to 0, the traverse run is invalid.
Summary of Contents for DK00 Series
Page 1: ...DK00 Series Inverter User Manual V1 3...
Page 5: ...4 2 4 Fault Alarm Reset 26 4 2 5 Keyboard digital setting modify...
Page 7: ...5 1 11 Serial Communication Settings 56...
Page 9: ...7 Maintenance 73 7 1 Inspect the inverter periodically73...
Page 11: ...9 3 Examples of MODBUS Information 100...
Page 13: ...Chart Index 109...
Page 25: ...1 2 Installation 2 3 Installation dimensions of inverter Chart 2 2 External dimension...
Page 85: ...72 Fault and trouble shooting...
Page 126: ...Chart Index 113 Chart 9 9 Error codes of serial communication 107...
Page 127: ...In order to improve our products constantly we remain the power of designs modified 3 8 2010...