102
MODBUS Communication Protocol
Command information
Slave address
02H
Function code
10H
Start address
Low byte
00H
Number
High byte
00H
Low byte
02H
data number
04H
Start data
High byte
00H
Low byte
01H
T h e n e x t d ata
High byte
00H
Low byte
01H
CRC-16
High byte
6CH
Low byte
EBH
R e m a r k s: D a ta n um b e r= q ua n t ity * 2
Slave address
02H
Function code
10H
Start address
High byte
00H
Low byte
00H
Number
High byte
00H
Low byte
02H
CRC-16
High byte
51H
Low byte
9FH
Slave address
02H
Function code
80H
Error code
01H
CRC-16
High byte
31H
Low byte
C2H
9.3.3 Write into multi-storage register
A maximum of 16 can be written into the contents of
inverter memory registers every time.
The specified data are written specified number into the
specified storage register . Write into data must in accordance with
the number order of register, respectively, according to a high 8 bits,
low 8bits order array in the instruction information.
From PLC to the slave2 of inverter modify 000H
、
001H
information of register,samples as below:
High byte 00H
Response information (normal)
Response information (fault)
Chart 9-6 write instruction samples of serial communication
Summary of Contents for DK00 Series
Page 1: ...DK00 Series Inverter User Manual V1 3...
Page 5: ...4 2 4 Fault Alarm Reset 26 4 2 5 Keyboard digital setting modify...
Page 7: ...5 1 11 Serial Communication Settings 56...
Page 9: ...7 Maintenance 73 7 1 Inspect the inverter periodically73...
Page 11: ...9 3 Examples of MODBUS Information 100...
Page 13: ...Chart Index 109...
Page 25: ...1 2 Installation 2 3 Installation dimensions of inverter Chart 2 2 External dimension...
Page 85: ...72 Fault and trouble shooting...
Page 126: ...Chart Index 113 Chart 9 9 Error codes of serial communication 107...
Page 127: ...In order to improve our products constantly we remain the power of designs modified 3 8 2010...