Detailed Function Description
53
P0-047
PID feedback channel
selection
Setting range
:
0
~
4
Factory value
:
0
0: AIN1 (0 ~ 10V). The PID feedback is set by the AIN1 voltage of
control terminal .
1: AIN1
(
4
~
20mA
)
. The PID feedback is set by the AIN1 current
of control terminal. Input current is automatically converted into
voltage, 4mA corresponds to 0V
,
20mA corresponds to 10V.
2: AIN2 (0 ~ 10V). The PID feedback is set by the AIN2 voltage of
control terminal .
3: AIN2
(
4
~
20mA
)
. The PID feedback is set by the AIN2 current
of control terminal. Input current is automatically converted into
voltage, 4mA corresponds to 0V
,
20mA corresponds to 10V.
4: Keyboard potentiometer (use when testing).
P0-048
Proportional gain P
Setting range:0.00~10.00
Factory value:1.00
P0-049
Integral time I
Setting range:0.00~100.00s
Factory value:2.00s
P0-050
Differential time D
Setting range:0.00~100.00s
Factory value:0.00s
The proportion, integral, differential in PID regulator is
Summary of Contents for DK00 Series
Page 1: ...DK00 Series Inverter User Manual V1 3...
Page 5: ...4 2 4 Fault Alarm Reset 26 4 2 5 Keyboard digital setting modify...
Page 7: ...5 1 11 Serial Communication Settings 56...
Page 9: ...7 Maintenance 73 7 1 Inspect the inverter periodically73...
Page 11: ...9 3 Examples of MODBUS Information 100...
Page 13: ...Chart Index 109...
Page 25: ...1 2 Installation 2 3 Installation dimensions of inverter Chart 2 2 External dimension...
Page 85: ...72 Fault and trouble shooting...
Page 126: ...Chart Index 113 Chart 9 9 Error codes of serial communication 107...
Page 127: ...In order to improve our products constantly we remain the power of designs modified 3 8 2010...