7
Summarize
Items
Criterion
Overload
capability
E100S series
:
150
%
rated current 60s;180
%
rated current 2s.
E100T series(G model)
:
150
%
rated current 60s
;
180
%
rated
current 2s.
E100T series(P model)
:
120
%
rated current 60s
;
150
%
rated
current 2s.
remark
:
may obtain the informations of model and power in
“
d1 function groups
”
.
Control Mode
Open-loop simple vector control
Torque boost
Manual torque can be adjust
;
Auto-Torque upgrade the whole
frequency band.
Start up Torque
when0.5Hz, rated torque for 150
%
.
Function
descriptions
Acc and Dec
time
0.1
~
3200.0s
Jog function
Jog frequency:0.00
~
50.00h z;
Standard
functions
Simple vector control
、
torque boost
、
a
utomatic slip
compensation
(
rev gain
)
、
stop for DC braking
、
Restart after
power off instantaneous
、
auto fault reset
、
control over-current
when accelerating speed
、
multi-step speed
4 run
、
traverse
frequency function applies to textile
、
closed loop PID control
Run rule
3kinds control mode
:
keyboard control, analog terminal
control, serial communication control
Frequency
Source
Selection
Digital setting, analog voltage setting, analog current setting,
the serial communication port setting; can be combined
through a variety of ways to switch.
Input
Terminals
4digital input terminals, as many as 13 kinds of custom
features, is compatible with the active NPN input;
Two analog input terminals, can receive a voltage signal (0 ~
10V), or current signal (4 ~ 20mA);
Summary of Contents for DK00 Series
Page 1: ...DK00 Series Inverter User Manual V1 3...
Page 5: ...4 2 4 Fault Alarm Reset 26 4 2 5 Keyboard digital setting modify...
Page 7: ...5 1 11 Serial Communication Settings 56...
Page 9: ...7 Maintenance 73 7 1 Inspect the inverter periodically73...
Page 11: ...9 3 Examples of MODBUS Information 100...
Page 13: ...Chart Index 109...
Page 25: ...1 2 Installation 2 3 Installation dimensions of inverter Chart 2 2 External dimension...
Page 85: ...72 Fault and trouble shooting...
Page 126: ...Chart Index 113 Chart 9 9 Error codes of serial communication 107...
Page 127: ...In order to improve our products constantly we remain the power of designs modified 3 8 2010...