Detailed Function Description
37
P0-015
Automatic slip
Setting range
:
0.0
~
Factory value
:
100.0
%
compensation gain
250.0
%
The function is used to improve the motor speed by reason of load
changes. When Load is stable, if the motor fluctuation of rotate
speed is large, please reduce the function code.
This function code for 0.0 mean that the automatic slip
compensation is prohibited.
5.1.3 Input terminals
P0-016
X1 terminal function
Setting range
:
0
~
14
Factory value
:
1
P0-017
X2 terminal function
Setting range
:
0
~
14
Factory value
:
2
P0-018
X3 terminal function
Setting range
:
0
~
14
Factory value
:
4
P0-019
X4 terminal function
Setting range
:
0
~
14
Factory value
:
9
0: invalid. Idle input terminals.
1: Forward run. Forward run command input.
2: Reverse run. Reverse run command input.