To use Com 3, connect the communication wires of the supplied RS485 cable to the
MP200 unit’s Com 3 port - see Figure 5.9. Set the port’s baud rate to 9600, address to
1, protocol to Modbus RTU or Modbus ASCII and mode to Slave using the communica-
tion software.
RS485 communication is viable for up to 4000 feet (1219 meters). Be sure to do the
following (see Section 5.1.2 for additional information on RS485 communication):
1. Connect the shield to the shield (S) terminal on the other device’s port. The (S) ter-
minal on the MP200 unit is used to reference its port to the same potential as the
source. Connect the shield to protective earth-ground at one point.
2. Provide termination resistors at each end, connected to the + and - lines. RT is
approximately 120 Ohms.
5.2: MP200 Metering System Communication and Programming
Overview
Only the basic MP200 metering system’s Device Profile settings are explained in this
manual. Refer to Chapter 10 in the
4.0 and MeterManager EXT
Software User Manual
for detailed instructions on configuring all settings of the MP200
Help>Contents
from the Communi-
cator EXT
TM
Main screen.
5.2.1: Connecting to the MP200 Unit through Communicator EXT
TM
Software
How to Connect:
1. Open the Communicator EXT
TM
software.
2. Click the
Connect
icon in the Icon bar.
Connect Icon