4: Electrical Installation
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
6. Service: Single Phase, 3-Wire Service with Direct Voltage and 1 CT
Connection for Metering 24 Single Phase Loads: MP200-S
NOTES:
• All CTs must have one side grounded to reduce shock hazard.
• You must order the MP200-S unit for single phase operation.
• EIG highly recommends using shorting blocks like the EI SB-6TC so that the meter
can be removed from service while the CT is energized.
I1-LO
LOADS
VL1
LINE
N
L(+) N(-)
I1-HI
VL1
I3-HI
I2-HI
I2-LO
VL2
I3-LO
SERVICE: SINGLE PHASE, 3-WIRE
CONNECTION TYPE: Direct Voltage, CTs
To monitor 24 individual loads.
See accuracy table for limiting factors.
Power Supply
Connection
Only one circuit is shown.
Duplicate for additional circuits.
Short Voltage inputs
together
Earth Ground
CT Shorting Block
EI# SB-6CT
Earth Ground
FUSE 3A
VL2
VL1
VL2
2
1
N
FUSES
2 x 0.1A
Run lines VL1 and VL2 through
the CT in opposite directions
Set PT ratio to half
in the meter.