Operating Instructions – MOVITRAC® LTP
11
4
Protection features
Mechanical Installation
4
Mechanical Installation
• Carefully inspect the MOVITRAC
®
LTP prior to installation to ensure it is undam-
aged.
• Store the MOVITRAC
®
LTP in its box until required. Storage should be clean and dry
and within the ambient temperature range –40 °C to +60 °C.
• Install the MOVITRAC
®
LTP on a flat, vertical, flame-resistant, vibration-free surface,
within suitable housing. This should be according to EN 60529 if specific Ingress
Protection ratings are required.
• Do not place flammable material close to the drive.
• The entry of conductive or flammable foreign bodies should be prevented.
• The maximum operational ambient temperature is 50 °C and the minimum is 0 °C.
• Relative humidity must be less than 95 % (non-condensing).
• MOVITRAC
®
LTP units can be installed side by side with their heatsink flanges
touching. This gives adequate ventilation space between them. If the
MOVITRAC
®
LTP is to be installed above another drive or any other heat-producing
device, the minimum vertical spacing is 150 mm. The enclosure should either be
force-ventilated or large enough to allow natural cooling (see chapter "IP20 / NEMA
1 housing: mounting and dimensions" on page 14).
Summary of Contents for MOVITRAC LTP series
Page 2: ...SEW EURODRIVE Driving the world...
Page 76: ......
Page 77: ......
Page 78: ......