50
Operating Instructions – MOVITRAC® LTP
9
MODBUS Control
Software
9.1.3
Register description
9.1.4
Monitor value registers
These registers are read only with command 03.
Type
Register
no.
Register title
Description
Read / Write
1
Drive command
0: CMD
Drive command setup:
00: stop, 01: start, 10: reset
1: CMD
2: 2nd
2nd deceleration ramp select flag
3 ... 15: Reserved
Reserved
2
Speed reference setup
This register holds the speed reference value with one decimal place
(200 = 20.0 Hz). The maximum speed reference value is limited by P1-01.
3
Torque reference setup
This register holds the torque reference with one decimal place (450 = 45.0 %).
The data range is from 0 (0 %) to 2000 (200.0 %).
This torque reference is only active when P4-06 = 3 and the drive is in vector
control mode.
4
Acc / Dec ramp setup
Ramp time in seconds (e.g. 100 = 10.0 s)
Read only
6
Drive status and error
code
High byte gives the drive error code (valid when the drive is tripped).
Low byte gives the drive status (0: drive stopped, 1: drive running, 2: drive
tripped).
7
Motor speed information This register gives motor speed information. The data is in Hz and with one
decimal place (e.g. 234 = 23.4 Hz).
8
Motor current
This register gives motor current information. The data is in Amps with one
decimal place (e.g. 87 = 8.7 A).
9
Motor torque
This register gives motor output torque information. It is a percentage value as
100.0 % equals motor rated torque. The data value is stated to one decimal
place.
10
Motor power
This register gives motor power information and the data is stated to 2 decimal
places (e.g. 124 = 1.24 KW / HP). The data unit depends on the drive type.
11
Digital input status
The value in this register represents the drive terminal digital input status (digital
input 1 ... 4). The lowest bit indicates digital input status 1.
Address
Description
Data format
Example
21
Bipolar analog input value
1 decimal place
156 = 15.6 %
22
2nd analog input value
1 decimal place
156 = 15.6 %
23
Speed control reference
–
156 = 156 %
24
1)
Digital speed reference
Internal value
–
25
Motor torque reference
–
2000 = 200.0 %
26
User PID reference
1 decimal place
156 = 15.6 %
27
User PID feedback
1 decimal place
156 = 15.6 %
28
User PID error input
1 decimal place
156 = 15.6 %
29
User PID P term output
1 decimal place
156 = 15.6 %
30
User PID I term output
1 decimal place
156 = 15.6 %
31
User PID D term output
1 decimal place
156 = 15.6 %
32
User PID output
1 decimal place
156 = 15.6 %
33
Motor output torque
–
1000 = 100.0 %
34
Magnetizing current
1 decimal place
156 = 15.6 A
35
Rotor current
1 decimal place
156 = 15.6 A
36
Field strength
1 decimal place
156 = 15.6 %
37
Stator resistance
3 decimal places
156 = 0.156 ohm