Operating Instructions – MOVITRAC® LTP
37
8
Parameter specifications:
Parameters
8.2.2
Extended parameters
Par.
Description
Range
Default
Explanation
P2-01
Digital input function select
0 ... 22
0
Defines the function of the digital inputs.
P2-02
Preset speed 2
–P1-01 ... +P1-01
0.0 Hz
Sets jog / preset speed 2
P2-03
Preset speed 3
–P1-01 ... +P1-01
0.0 Hz
Sets jog / preset speed 3
P2-04
Preset speed 4
–P1-01 ... +P1-01
0.0 Hz
Sets jog / preset speed 4
P2-05
Preset speed 5
–P1-01 ... +P1-01
0.0 Hz
Sets jog / preset speed 5
P2-06
Preset speed 6
–P1-01 ... +P1-01
0.0 Hz
Sets jog / preset speed 6
P2-07
Preset speed 7
–P1-01 ... +P1-01
0.0 Hz
Sets jog / preset speed 7
P2-08
Preset speed 8
–P1-01 ... +P1-01
0.0 Hz
Sets jog / preset speed 8
P2-09
Skip frequency
P1-02 ... P1-01
0.0 Hz
Centre point of skip frequency band set up
in conjunction with P2-10.
P2-10
Skip frequency band
0 ... P1-01
0.0 Hz
(disable)
Width of skip frequency band centred on
frequency set in P2-09.
P2-11
Analog output /
Digital output 1
Function select
(Digital output mode)
7
Digital output mode. Logic 1 = DC +24 V
0:
Drive enabled
0: Logic 1 when drive enabled (running)
1:
Drive healthy
1: Logic 1 when no fault condition exists on
drive
2:
Motor at target speed
2: Logic 1 when motor speed matches set-
point speed
3:
Motor speed > 0
3: Logic 1 when motor runs above zero
speed
4:
Motor speed
≥
limit
4 - 6:
Digital output enabled using level set in
P2-12h and P2-12L
5:
Motor torque
≥
limit
6:
2nd analog input
≥
limit
(Analog output mode)
(Analog output mode)
1)
1) Analog output format refers to P2-36
7:
Motor speed
7: Motor speed, 0 ... 10 V = 0 ... P-01
8:
Motor torque
8: Motor torque, 0 ... 10 V = 0 ... 200 % of
motor rated torque
9:
Motor power (kW)
9: Motor power, 0 ... 10 V = 0 ... 150 % of
drive rated power
10:
Motor current
10: Motor current, 0 ... 10 V = 0 ... 200 % of
P1-08
P2-12(h)
Digital output control high
limit
Speed : 0 ... 200 %
(200 % = max speed)
Torque : 0 ... 200 %
(200 % = rated torque)
PID feedback : 0 ... 200 %
(200 % = max 2nd analog input)
100 %
Digital output state set to logic 1 when
selected value in P2-11 larger than this
limit.
Limit in P2-12 relates to speed if P2-11 = 4,
to motor torque if P2-11 = 5 or to the PID
feedback value (2nd analog input) if
P2-11 = 6.
P2-12(L)
Digital output control low
limit
0 … P2-12(h)
100 %
Digital output state back to logic 0 when
selected value in P2-11 less than or equal
to this limit. (P2-11 = 4,5 or 6)
P2-13
User relay output function
select
0:
Drive Enabled
1
If P2-15 = 0 (Normally Open), the relay
contacts are closed when the selected con-
dition is fulfilled.
If P2-15 = 1 (Normally Closed), the relay
contacts are open when the selected condi-
tion is fulfilled.
1:
Drive healthy
2:
Motor at target speed
3:
Motor speed > 0
4:
Motor speed
≥
limit
5:
Motor torque
≥
limit
6:
2nd analog input
≥
limit
P6..
P60.
P600