Operating Instructions – MOVITRAC® LTP
53
9
MODBUS Control
Software
9.1.6
Internal value
For some speed related parameters, the drive uses an internal value instead of the ac-
tual speed in Hz in order to increase the resolution. In order to set these speed related
parameters correctly, the internal value must be used instead of the display value.
Speed Internal = Speed in Hz x Factor
199
Control mode
0, 1, 2
0: Vector speed control
1: Vector torque control
2: V/f speed control
–
200
Motor parameter auto-tune
0 or 1
–
–
201
Speed controller P-gain
0 ... 4096
–
–
202
Speed controller integral time
constant
0.001 ... 0.100 s
–
1 = 0.001 s
203
Motor power factor
0.50 ... 0.99
–
78 = 0.78
204
Torque reference select
0 ... 3
0: Digital preset value
1: Bipolar analog input
2: 2nd analog input
3: MODBUS reference
–
205
Maximum torque limit / ref
0 ... 200 %
–
100 = 100 %
206
Minimum torque limit
0 ... 150.0 %
–
100 = 10.0 %
207
V/f characterisitic adjustment
frequency
0 ... P1-09
–
500 = 50.0 Hz
208
V/f characterisitic adjustment
voltage
0 ... P1-07
–
100 = 100 V
1) See chapter 9.1.6 "Internal value"
Adr
Description
Data range
Data format
Example
When P1-09
≤
100 Hz
Factor = 60
e.g. 30.5 Hz = 1830
When P1-09 is 101 ... 199 Hz
Factor = 30
e.g. 30.5 Hz = 915
When P1-09
≥
200 Hz
Factor = 15
e.g. 250 Hz = 3750