Operating Instructions – MOVITRAC® B
5
Keypads
Startup
•
DANGER
Parameter settings incorrect due to unsuitable data sets.
Severe or fatal injuries.
– Make sure that the data set you copy is suitable for the application.
10. Enter the following motor nameplate data:
• C10* Observe rated motor current, connection
type
or
.
• C11* rated motor power
• C12* power factor cos
φ
• C13* rated motor speed
C47*4-Q OPERATION
NO
YES
11. Enter the nominal voltage of the supply system (C05*
for SEW motor, C14* for non-SEW motor).
C05* V
NOM. LINE VOLT. 1
+400,000
11. Start the calculation for the startup data by choosing
"YES". The process lasts a few seconds.
C06*CALCULATION
NO
YES
FOR SEW MOTORS
12. The calculation is performed. After calculation, the
next menu item appears automatically.
C06*SAVE
NO
YES
FOR NON-SEW MOTORS
12. For non-SEW motors, a calibration process is re-
quired to perform the calculation:
• The motor is energized automatically.
13. Set "SAVE" to "YES". The data (motor parameters)
are copied to the non-volatile memory of
MOVITRAC
®
.
DATA IS
BEING COPIED...
14. The startup procedure is now complete. Use the DEL
key to return to the context menu.
MANUAL MODE
STARTUP
COPY TO DBG
COPY TO MC07B
15. Use the
↓
key to scroll down until the menu item
"EXIT" is selected.
UNIT SETTINGS
QUIT
16. Confirm your selection by pressing OK. The basic dis-
play appears.
0.00rpm
0.000Amp
CONTROLLER INHIBIT
00
I