4
Installation
Connection braking resistor BW.. / BW..-T
Operating Instructions Basic Unit – MOVITRAC
®
B
19
4.6
Connection braking resistor BW.. / BW..-T
Overload protection for braking resistors BW:
T
2
T
1
BW...-...-T
RB2
RB1
X2:
U
V
W
+R -R
BW...
F16
X2:
U
V
W
+R -R
(X3:)
(X3:)
PE
PE
Has effect
on K11
M
3-phase
Has effect
on K11
When the internal thermostat triggers,
K11 must be opened and DIØØ "Controller
inhibit" must have a "0" signal. The
resistance circuit must not be interrupted!
When the external bimetallic relay (F16)
triggers, K11 must be opened and
DIØØ "controller inhibit" must have a
"0" signal. The resistance circuit must
not be interrupted!
Overload protection
Braking resistor
type
Design
specified
Internal thermostat
(..T)
External bimetallic relay
(F16)
BW...
–
–
Required
BW...-...-T
1)
1) Permitted mounting options: On horizontal or vertical surfaces with brackets at the bottom and perforated
sheets at top and bottom.
Mounting not permitted:
on vertical surfaces with brackets at the top, right or
left.
–
One of the two options (internal thermostat / external bimetallic
relay) is required.
BW...-003 / BW...-005
Adequate
–
Permitted