7
Technical data
MOVITRAC® B technical data
38
Operating Instructions Basic Unit – MOVITRAC
®
B
7.4.7
AC 400/500 V / 3-phase / size 0L / 2.2 ... 4.0 kW / 3.0... 5.0 HP
MOVITRAC
®
MC07B (3-phase supply system)
0022-5A3-4-00
0030-5A3-4-00
0040-5A3-4-00
Part number
828 521 7
828 522 5
828 523 3
INPUT
Permitted rated supply voltage
U
N
3 × AC 400 V
V
Mains
= AC 380 V – 10 % ... AC 500 V + 10 %
Rated supply frequency
f
N
50 / 60 Hz ± 5 %
Rated mains current 3-phase with
V
Mains
= AC 400 V
AC 5.0 A
AC 6.3 A
AC 9.5 A
OUTPUT
Output voltage
V
A
3 × 0 ... V
Mains
Recommended motor power under constant
load (with V
Mains
= AC 400 V)
P
Mot
2.2 kW
3.0 HP
3.0 kW
4.0 HP
4.0 kW
5.0 HP
Rated output current
with V
Mains
= AC 400 V
I
N
AC 5.5 A
AC 7.0 A
AC 9.5 A
Minimum permitted braking resistor value
(4-Q operation)
R
BW_min
68
Ê
GENERAL INFORMATION
Power loss at I
N
P
V
97 W
123 W
155 W
Current limitation
150 % I
N
for maximum 60 seconds
Connections
Terminals
4 mm
2
/ AWG12
Dimensions
W × H × D
80 × 273.5 × 163 mm / 3.1 × 10.8 × 6.4 in
Weight
m
2.1 kg / 4.6 lbs.
80
163.5
273.5
284.5
324.5
308.5
70
159.5
149
6
P
i
f
kVA
Hz
n