Technical data
MOVITRAC® B electronics data
Operating Instructions Basic Unit – MOVITRAC
®
B
31
7.3
MOVITRAC
®
B electronics data
Function
Terminal Designa-
tion
Default
Data
Setpoint input
(differential input)
X10:1
X10:2
X10:3
X10:4
REF1
AI11 (+)
AI12 (0)
GND
0 ... +10 V (R
i
> 200 k
Ê
)
0 ... 20 mA / 4 ... 20 mA (R
i
= 250
Ê
)
Resolution 10 Bit, sample cycle 1 ms
GND = Reference potential for binary and analog
signals, PE potential
Binary inputs
X12:1
X12:2
X12:3
X12:4
X12:5
X12.6
DI00
DI01
DI02
DI03
DI04
DI05TF
Error reset
CW/Stop
CCW/Stop
Enable/Rapid
stop
n11/n21
n12/n22
Ri = 3 k
Ê
, I
E
= 10 mA, sample cycle 5 ms,
PLC compatible
Signal level according to EN 61131-2 type 1 or 3:
•
+11 ... +30 V
Æ
1 / contact made
•
–3 ... +5 V
Æ
0 / contact open
•
X12:2 / DI01 with fixed assignment CW/Stop
•
X12:5 / DI04 can be used as frequency input
•
X12:6 / DI05 can be used as TF input
Supply voltage for TF
X12:7
VOTF
Special characteristics for TF according to
DIN EN 60947-8
Auxiliary supply
output / External
voltage supply
X12:8
24VIO
Auxiliary supply output: V = 24V DC,
current carrying capacity I
max
= 50 mA
External voltage supply:
V = 24V DC –15 % / +20 % to EN 61131-2
Reference terminal
X12:9
GND
Reference potential for binary and analog signals,
PE potential
Binary outputs
X13:1
X13:2
X13:3
X13:4
GND
DO02
DO03
GND
Brake released
Ready for
operation
PLC compatible, response time 5 ms,
I
max
DO02 = 150 mA, I
max
DO03 = 50 mA,
short-circuit proof, protected against external
voltage up to 30 V
GND = Reference potential for binary and
analog signals, PE potential
Relay output
X13:5
X13:6
X13:7
DO01-C
DO01-NO
DO01-NC
Shared relay contact
NO contact
NC contact
Load capacity: V
max
= 30 V, I
max
= 800 mA
Safety contact
(from BG2S / in
preparation)
X17:1
X17:2
X17:3
X17:4
Reserved
Terminal response
times
Binary input and output terminals are updated every 5 ms
Max. cable
cross-section
1.5 mm
2
(AWG15) without conductor end sleeves
1.0 mm
2
(AWG17) with conductor end sleeves